3000V103-UK 13
Type
Max. power
dissipation
Max. required
power
3101 0.52 0.52
3102 0.52 0.52
3111 0.70 0.70
3112 0.70 0.70
3113 0.70 0.70
3331 0.80 0.80
3333 0.80 0.80
3337 0.80 0.80
Common electrical specifications:
Supply voltage, 24 VDC nom. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16.8...31.2 VDC
Loop-powered:
3331. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.5...35 VDC
3333. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.3...35 VDC
3337. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.2...35 VDC
Power requirements:
Max. required power is the maximum power needed at power supply terminals or rail connector.
Max. power dissipation is the maximum power dissipated at nominal operating values.
Isolation voltage, test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.5 kVAC
Isolation voltage working. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300 VAC (reinforced) /
250 VAC (Zone 2, Div. 2)
Double isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Input / output 1 / output 2 / supply
Signal dynamics, input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 bit
Signal dynamics, output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 bit
Signal / noise ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Min. 60 dB
Long-term stability, better than (only 3113) . . . . . . . . . . . . . . . . . . . ±0.1% of span / year (±0.3% of span / 5 years)
Incorrect DIP-sw setting identification:
Supplied . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 V / 0 mA output; LED 0.5 s / 1 Hz
Loop-powered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.5 mA output
Response time
Selectable
HART read only
mode
HART mode
< 30 ms < 300 ms < 60 ms 0.06...60 s
3101
3102
3111
3112
3113
3331
3333
3337