DESCRIPTION:
SP-500 is an electronically activated trap priming device. Primer functions in conjunction with EMS, delivering potable
water across an air gap funnel.
CAUTION: SP-500 should not be dened as pressure feed trap priming system. Device must be installed a minimum
of 12" above ood level of device being served. Trap primer should be mounted one foot above the nished oor for
every 20 feet of trap priming line, measured from bottom of air gap.
OPERATION:
EMS activated solenoid valve discharging potable water to P-trap
INSTRUCTIONS PERTAINING TO A RISK OF FIRE ELECTRIC SHOCK, OR INJURY TO PERSONS
*** IMPORTANT SAFETY INSTRUCTIONS ***
*** SAVE THESE INSTRUCTIONS ***
WARNING - When using electric appliances, basic precautions should always be followed, including the
following:
a) Read all of the instructions before using the appliance.
b) Do not contact moving parts.
c) Only use attachments recommended or sold by the manufacturer
d) Do not use outdoors.
To disconnect turn all controls to the o position, then remove from connection.
Disconnect power before servicing or cleaning.
Do not operate any appliance with a damaged cord, or after the appliance malfunctions or is dropped or
damaged in any manner. Return appliance to the nearest authorized service facility. For examination, repair,
or electrical or mechanical adjustment.
e) For a permanently connected appliance - Turn the power switch to the o position when the appliance is not in
use and before servicing or cleaning.
f) For a grounded appliance - Connect to a properly grounded outlet only. See grounding instructions.
GROUNDING INSTRUCTIONS
This appliance must be connected to a grounded metal, permanent wiring system; or an equipment-grounding
conductor must be run with the circuit conductors and connected to the equipment-grounding terminal or lead on the
appliance.
SAVE THESE INSTRUCTIONS
INSTALLATION:
1) Primers minimum elevation above oor rim of drain served shall be one foot. Device must be installed a
minimum of 12" above ood level of device being served. Trap primer should be mounted one foot above the
nished oor for every 20 feet of trap priming line, measured from bottom of air gap.
2) Solo-prime must be installed in an accessible location. For access door applications use 8” x 14” model D814
prime coat or stainless steel.
3) Connect ½” male NPT tting (primer supply) to fresh water line, using Teon tape. Connect priming discharge
line (minimum ½”) to inlet side of oor drain being served (not supplied). Ensure discharge line is properly
sloped downward to the discharge point.
4) Connect primer drain line, distribution unit or PM manifold to system, ensure assembly is plumb and square.
5) Wire primer to Energy Management System, follow N.E.C. and local codes.
1044
WATER HAMMER
ARRESTORS
TEMPERA
ANTI-SCALD VALVES
BAC-2-BAC
MANIFOLDS
TRAP PRIMER VALVES
AND MANIFOLDS
THERMOSTATIC
MIXING VALVES
Solo Prime Electronic Trap Priming System
Installation & Maintenance Instructions
U
.
S
.
G
R
E
E
N
B
U
I
L
D
I
N
G
C
O
U
N
C
I
L
U
S
G
B
C
®
Question and Answer IconNeed help?

Do you have a question about the Precision Plumbing Products MP-500 PRIMER and is the answer not in the manual?

Precision Plumbing Products MP-500 PRIMER Specifications

General IconGeneral
BrandPrecision Plumbing Products
ModelMP-500 PRIMER
CategoryPlumbing Product
LanguageEnglish

Summary

Safety and Operating Instructions

General Safety Precautions

Basic safety precautions for using electric appliances, including reading instructions and avoiding hazards.

Grounding Instructions

Requirements for connecting the appliance to a grounded electrical system for safety.

Installation Guide

Primer Elevation and Placement

Specifies minimum elevation and accessible location requirements for the trap primer.

Water Line and Discharge Connections

Details connecting the water supply, primer discharge line, and drain/manifold systems.

Electrical Wiring

Instructions for wiring the primer to the Energy Management System per codes.

Power and Timing Specifications

Power Requirements

Details the voltage and wattage specifications for the trap priming system.

Timing and Cycle Recommendations

Guidance on recommended cycle times for primer output based on floor drain applications.

Delivery Rate Specifications

Delivery Rate per 6 Second Function

Specifies the volume of water delivered by the primer at different pressure levels.