MAV 103 ZC 205 ZC 207 ZC 208 ZC 311 ZC 312 ZC 316 ZC 317 ZC 320 ZA 425 ZA 433 ZA 440 ZA
Puissance frigorifique nominale
Nominal cooling capacity
(1) kW 0,99 1,65 2,03 1,91 2,90 2,66 4,17 4,07 5,05 6,51 7,26 9,37
Volume de la cave
Celar volume
(2)
56 810 1015 1015 1523 1523 2540 2540 3140 4062 4470 5690
Raccordements
Connections
Liquide
Lquid
inch 1/4" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 1/2" 1/2" 1/2"
Aspiration
Suction
inch 3/8" 3/8" 3/8" 3/8" 1/2" 1/2" 1/2" 1/2" 5/8" 3/4" 3/4" 3/4"
GROUPE DE CONDENSATION - CONDENSING UNIT
Modèle
Model
GAV
103 ZC
GAV
205 ZC
GAV
207 ZC
GAV
207 ZC
GAV
311 ZC
GAV
311 ZC
GAV
316 ZC
GAV
316 ZC
GAV
320 ZA
GAV
425 ZA
GAV
433 ZA
GAV
440 ZA
Compresseur
Compressor
Type
Type
ML80TB MP12TB MX16TB MX16TB MX21TB MX21TB
CAJ
4519
Z-F
CAJ
4519
Z-F
TFH
4524
Z-Y
TFH
4531
Z-Y
TFH
4540
Z-Y
TAG
4546
Z-Y
Puissance
Power
hp 3/8 1/2 5/8 5/8 1 1/8 1 1/8 1 1/2 1 1/2 2 2 1/2 3 4
Tension
Supply
230V/~1/50Hz 400V/~3/50Hz
Id (3) A 12,8 17,0 27,0 27,0 33,0 33,0 31,0 31,0 24,0 26,5 44,0 40,0
Imax (4) A 4,0 6,0 8,4 8,4 11,0 11,0 15,4 15,4 6,3 8,2 9,2 11,4
Ventilateur
Fan
Nbre x diatre
No. x diameter
mm
1x Ø240 1x Ø300 1x Ø300 1x Ø300 1x Ø355 1x Ø355 1x Ø355 1x Ø355 1x Ø355 1x Ø450 1x Ø450 1x Ø450
Débit d'air
Air flow
m³/h 550 800 800 800 1780 1780 1780 1780 1780 3170 3170 3170
Tension
Supply
230V/~1/50Hz
Puissance utile
Useful power
W 18 35 35 35 110 110 110 110 110 260 260 260
Imax (4) A 0,48 0,75 0,75 0,75 1,2 1,2 1,2 1,2 1,2 2,15 2,15 2,15
DESP 97/23/CE Cat. Risque
PED 97/23/EC Risk Cat.
I I I I I I I I I I I II
Niveau sonore
Sound level
(5) dB(A) 33 35 36 36 39 39 43 43 42 44 48 51
Dimensions
Dimensions
L mm 588 658 658 658 788 788 788 788 788 1046 1046 1046
P mm 470 487 487 487 577 577 577 577 577 672 672 672
H mm 348 368 368 368 468 468 468 468 468 588 588 588
Poids
Weight
kg 38 40 50 50 66 66 68 68 76 98 100 112
Colisage
Casing
L mm 590 660 660 660 790 790 790 790 790 1250 1250 1250
P mm 561 561 561 561 651 651 651 651 651 725 725 725
H mm 350 380 380 380 480 480 480
480 480 715 715 715
EVAPORATEUR - COOLER UNIT
Modèle
Model
BP 145 BP 215 BP 290
DFC
14 6P
BP 290
DFC
14 6P
BP 415
DFC
24 6P
DFC
34 6P
DFC
34 6P
DFC
44 6P
DFC
54 6P
Ventilateur
Fan
Nbre x diatre
No. x diameter
mm
2x Ø200 3x Ø200 4x Ø200 1x Ø300 4x Ø200 1x Ø300 4x Ø240 2x Ø300 3x Ø300 3x Ø300 4x Ø300 4x Ø300
Débit d'air
Air flow
m³/h 1000 1500 2000 770 2000 770 3000 1540 2310 2310 3080 3850
Tension
Supply
230V/~1/50Hz
Puissance utile
Useful power
W 7 7 7 25 7 25 18 25 25 25 25 25
Imax (4) A 0,40 0,60 0,80 0,28 0,80 0,28 1,02 0,56 0,84 0,84 1,12 1,40
Niveau sonore
Sound level
(5) dB(A) 30 32 33 35 33 35 38 38 40 40 41 42
Dimensions
Dimensions
L mm 780 1130 1440 700 1440 700 1440 1100 1500 1500 1900 2300
P mm 487 487 487 810 487 810 470 810 810 810 810 810
H mm 235 235 235 240 235 240 305 240 240 240 260 260
Poids
Weight
kg 26 37 49 32 38 32 37 38 49 49 73 73
Colisage
Casing
L mm 800 1160 1470 800 1470 1200 1470 1200 1600 1600 2000 2400
P mm 610 610 660 900 660 900 660 900 900 900 900 900
H mm 320 320 390 390 390 390 390 390 390 390 390 390
CARACTERISTIQUES TECHNIQUES
TECHNICAL DATA
APPLICATION CAVE A VIN WINE CELLAR APPLICATION
CARACTERISTIQUES TECHNIQUES
TECHNICAL DATA
(1) Conditions nominales au R404A : Température de cave +12°C. Température extérieure +32°C.
(2) A titre indicatif.
(3) Intensité de démarrage (courant rotor bloqué) du compresseur.
(4) Intensité max. de fonctionnement.
(5) Les niveaux de pression acoustique (en dBA à 10 mètres) sont indiqués en champ libre.
Le fonctionnement à un régime différent de ces conditions nominales peut conduire à des résultats différents.
Les résultats obtenus sur le lieu de l'installation peuvent être différents par rapport aux valeurs du catalogue, du
fait de phénomènes de réflexion (présence de mur, etc ...).
L'affaiblissement du niveau sonore en fonction de la distance est théorique et les phénomènes de réflexion et de
résonnance peuvent modifier le résultat, soit au niveau global pondéré, soit sur certaines fréquences.
(1)NominalcapacitieswithR404A:Celartemperature+12°C.Ambientairtemperature+32°C.
(2) For information only.
(3) Locked Rotor current of compressor.
(4) Max. operating current.
(5) The sound presure levels (in dB(A) at 10 meters) are mentioned in free field.
Running the equipment in conditions differing from these nominal values may lead to different results.
The results obtained on the installation site may differ from those in this leaflet, due to sound reflections from
walls, etc.
The reduction of sound level as a function of distance is theoretical and sound reflection and resonance may
alter the results, either on total sound level or on certain frequencies.