Advanced Test Products Europe RG3000-E
- 6 -
OPERATING YOUR RG3000-E
Procedure for Purging Remaining Refrigerant From the RG3000-E
1. Close the valves of the system being serviced that are connected to the inlet
valve of the RG3000-E.
2. Close the inlet valve on the RG3000-E. The outlet valve should remain open.
3. Run the unit until desired vacuum is achieved.
4. Turn the RG3000-E off.
5. Close the valves on the recovery tank and the outlet valve on the RG3000-E.
6. Disconnect and store all hoses.
7. Replace the in-line filter on your RG3000-E after each time excessive contaminant
is encountered.
Important Note
We strongly recommend the use of Robinair hoses with Quick Seals™ to avoid wasting
refrigerant because of their unique reverseable, built-in, check valve.
RA69060A - set of 3 hoses wit Quick Seals™ Red, Yellow and Blue; 152cm long.