5
5.1.2 For model LIF5800RL/2; Connecting the smoke alarm on the base plate will
activate the lithium battery. Please note, the long absence of mains power may
damage the rechargeable battery. Warranty is void if the battery is
damaged. If the mains power is turned off for a long period of time, for
example, if the building is not occupied, disconnect the smoke alarm from the
base plate. When mains power is turned on, ensure the smoke alarm is then
connected to the base plate. The battery may be low in new smoke alarms,
please allow up to 8 hours for the battery to fully charge. Smoke alarms may
chirp until the battery is fully charged. When recharging do not press
Test/Hush button.
5.1.3 This Smoke Alarm can only interconnect with PSA Products LIFESAVER
range of smoke alarms, heat alarm and accessories. Interconnection with other
brands may cause damage or result in a shock or fire risk and void warranty.
5.1.4 Due to “noise” from electromagnetic interference, up to 24 units of smoke
alarms and compatible products may be interconnected.
5.1.5 There are five terminals in the supply terminal block, marked 9V, A, SW, N,
LOOP. It is important that the alarm be wired correctly to ensure correct
operation. Incorrect wiring to the Smoke Alarm will damage the unit and void
the warranty.
5.1.6 A total maximum of 250 meters (820 feet) of wire can be used in interconnect-
ing smoke alarms.
5.1.7 All final sub-circuit conductors including the signal conductor must be a
minimum size of 1mm² with 250V grade insulation.
5.1.8 Interconnected Smoke Alarms must be connected to the same final subcircuit.
5.1.9 Do not use any wire that could later be confused with the normal house wires
for the interconnect wire. For example, green/yellow earth wire.
5.1.10 Do not connect AC power wires to SW interconnect terminal. These will
damage smoke alarms.
5.1.11 Do not connect the SW interconnect wire to any device, except the SW
interconnect terminal of smoke alarm. Otherwise, smoke alarm will be
damage.
5.1.12 Switch wire (SW) only can drive the RK10A/9 and smoke alarms.
5.1.13 Do not connect 9V wire to AC power or SW interconnect terminal.
This will damage the smoke alarms.
5. INSTALLATION
1398-7211-01_B2_V2:_ 2017.9.7 3:55 PM Page 5