Pulsar Quick Start Manual - Blackbox Series
Congratulations on your purchase of a
Pulsar Blackbox!
This quality system has been developed with the
latest digital ultrasonic technology for liquids,
slurries, and solids. No more noise and beam
angle issues.
It provides non-contacting level (volume in-
cluded with the keypad/display version) with 2
user-defined relays. Comes standard with
110VAC, 12VDC and 24VDC power. Options:
4-20mA, 0-5VAC, Modbus RTU, Profibus dP,
and Ethernet output versions are available.
LIQUIDS and SOLIDS
Mount the transducer away from any obstructions, fal-
ling water/solids, rough walls, pumps, switches, etc…
Visualize looking down the echo path of the transducer
and seeing a nice clear shot (2’+ dia.) to the very bot-
tom during fill and empty cycles.
Ensure the maximum level does not come within the
minimum dB blanking distance.
Confirm the inside of the standpipe is smooth and does
not have any protrusions at the weld.
Do not hang the transducer by the cable.
Typically, mount the dB transducer 1/2 the tank radius.
(Call Pulsar Technical Support for Special Service
Passcode and Instructions 850-609-1777.)
LIQUIDS
Dome top tanks will require Gain & Algorithm change.
If reading false level, use P21 and set true distance
SOLIDS
Consult factory if the silo is extremely dusty—we can
increase the return signal strength (even during fill).
DATEM may map-out the true echo. Use P21 to set
true distance and turn “Update Datem” off!
If acoustically noisy, change Algorithm to Largest.
TRANSDUCER WIRING
TERMINAL IF SPLICING
RED = POWER RED = BLACK
WHITE = SIGNAL WHITE = WHITE
BLACK & GREEN = 0V BLACK & GREEN = SHIELD
Use any standard, 2 conductor/shielded pair for splic-
ing (recommend 18 AWG gauge, UV protected)
Use 16 AWG gauge if going 500 - 3,000 ft cable run.
Transducer shield is required - do not cut or float!
Confirm Mains Voltage Selector is set to 115VAC.
.5-10 ft 1-20 ft 1-33 ft 1.7-50 ft 2-82 ft 3-132 ft
dB 3 dB 6 dB 10 dB 15 dB 25 dB 40 Aiming Kit
Pulsar, Inc., PO Box 799, Shalimar, FL 32579 Phone: (850) 609-1777 Fax: (850) 651-4777 support@pulsar-us.com
Blind Version
TRANSDUCER INSTALLATION TROUBLESHOOTING