MODBUS Interface
F-14 Verbatim Owner's Manual
4 5 ZZ 5 N
Function Set channel number ZZ analog low alarm set point to N. Use
N = -0 to clear. Omit N to read current set point value.
Response remote channel <ZZ> low set point is <N>
4 5 ZZ 6 N
Function Set channel number ZZ analog high alarm set point to N. Use
N = -0 to clear. Omit N to read current set point value.
Response remote channel <ZZ> high set point is <N>
F.10.3 Linking Remote Channels to Phone Numbers
4 5 ZZ 9
Function Read RC number ZZ alarm call grouping linkage.
Response remote channel <ZZ> calls <list>
4 5 ZZ 9 DN
Function Link RC number ZZ to phone number list DN
Response remote channel <ZZ> calls <list>
4 5 ZZ 9 *
Function Clear all RC number ZZ phone number linkages
Response remote channel <ZZ> calls all phone numbers
Note:
Linking Remote Channels to phone numbers is different than linking one
Remote Channel to another Remote Channel. The latter is discussed in
section F.12.
F.11 Alarm Trip Delays
The alarm trip delay commands here apply only to criteria violations. See code
4907 for the COMALARM trip delay. See codes 4921 and 4922 for network
alarming.
4 6 ZZ
Function Reads channel number ZZ alarm trip delay.
Response remote channel <ZZ> alarm trip delay is <v> seconds
4 6 ZZ *
Function Sets channel number ZZ alarm trip delay to 2.0 seconds.
Response remote channel <ZZ> alarm trip delay is 2.0 seconds
4 6 ZZ V
Function Sets RCZZ individual alarm trip delay to V.
Response remote channel <ZZ> alarm trip delay is <V> seconds