Programming and Testing
3-4 Verbatim Owner's Manual
All contact inputs are initially set normally closed (i.e. they will alarm on Open
Circuit). This is the default setting and, therefore, any open circuits, including
any inputs left disconnected during installation, will appear as alarms until the
inputs are programmed.
K To automatically program the inputs:
Make sure all inputs are in their normal (non-alarm) state. Then press:
5 0 0 ENTER
The Verbatim autodialer automatically examines all inputs and programs them
to alarm on the opposite input state from their present status. This code 500
does not affect any channels that have been programmed for Disabled Channels,
Status Only, Run Time Meter, or Pulse Totalizer function.
L Exceptions
In most cases, no further programming of contact inputs is necessary.
However, the following configuration options are available:
To set any input to be disabled and never be annunciated, press:
5 ZZ 0 ENTER
where ZZ is the 2 digit channel number you are programming. Be sure to
always use a leading 0 for channels 1 through 9 to keep the channel
number a two-digit entry.
To set an individual contact input for normally closed operation (i.e. to
alarm on Open Circuit), press:
5 ZZ 1 ENTER
K To set an individual contact input channel for normally open operation
(i.e. to alarm on Closed Circuit), press:
5 ZZ 2 ENTER
K To set inputs to report status only, program each individual channel as
follows:
5 ZZ 3 ENTER
This setup never causes an alarm to dial out.
K To set contact inputs for the run-time meter function, program each
channel as follows:
5 ZZ 4 ENTER