P.C.B. SM 20015 – boiler settings
5
Parameter 1 setting: BOILER TYPE SELECTION
To modify the Parameter value:
a. Put ON/OFF button
1 in OFF position ( );
b. Push pad 6 and simultaneously and keep them pressed;
c. Put ON/OFF button
1 in ON position ( ) and wait until the display shows - ;
d. Release pad
6 and ;
e. Keeping pad
5 pressed, press pad 6 and select parameter no. ;
f. Release service pad
5 ; press and release service pad 5 ;
g. The display
will show the parameter value to be set or modified;
h. Press pad
6 or to modify (increase or decrease) the parameter value instantaneous type, storage type or storage
type comfort;
i. Press and release service pad
5 to confirm setting;
j. The display will show parameter no.
;
k. Position ON/OFF button
1 first in OFF position ( ) and back to ON position ( );
Parameter 2 setting: GAS TYPE SELECTION
To modify the Parameter value:
a. Put ON/OFF button 1 in OFF position ( );
b. Push pad 6 and simultaneously and keep them pressed;
c. Put ON/OFF button
1 in ON position ( ) and wait until the display shows - ;
d. Release pad
6 and ;
e. Keeping pad
pressed, press pad 6 and select parameter no ;
f. Release service pad
5 ; press and release pad service ;
g. The display
will show the parameter value to be set or modified;
h. Press pad
6 or to modify (increase or decrease) the parameter value NATURAL GAS, L.P.G ;
i. Press and release service pad
to confirm setting;
j. The display will show parameter no.
;
k. Position ON / OFF button 1 first in OFF position ( ) and back to ON position ( );
P