Do you have a question about the RadioLink Ei168 and is the answer not in the manual?
Test Button | Yes |
---|---|
Type | Photoelectric |
Alarm Volume | ≥85dB at 3 meters |
LED Indicator | Yes |
Alarm Sound Level | 85dB |
Operating Temperature | 0°C |
Humidity Range | 10% (non-condensing) |
Install each RadioLINK Base in the ceiling at least 0.30m from light fittings and connect to mains circuit.
Slide alarm onto the Ei168 RadioLINK Base to activate rechargeable back-up cells.
Insert screwdriver into house code switch slots of each unit within 15 minutes to activate house code mode.
Press the button test on each alarm to ensure all units are communicating.
Select a location for the RadioLINK Base as advised in the Smoke/Heat Alarm instruction leaflet.
Ensure test button is held down until amber light comes on continuously for 3.5 seconds.
Convert a centrally located RadioLINK Base into a Repeater as per Section 4.
Extend the flexible antenna from the base housing and position it flat against the ceiling.
Re-locate or rotate units to improve signal reception, moving them away from metal surfaces or wiring.