Finned copper tube gas boilers & water heaters – Boiler Manual
14
Relief Valve
Pipe the discharge of the pressure relief valve to prevent scalding in
the event of a discharge, see Figure 10. e discharge piping must be
sized the same as the pressure relief valve outlet and installed to allow
complete drainage of both the relief valve and the discharge piping.
Figure 10 Relief Valve Piping
Never install any type of valve between the boiler/
water heater and the relief valve or an explosion causing
extensive property damage, severe personal injury or
death may occur!
Flow Switch
e ow switch supplied with the boiler/water heater must be wired
to the terminal strip in the control panel to prevent the boiler from
ring unless theres adequate water ow through the unit. e ow
switch must be installed in the supply piping adjacent to the boiler
outlet connection.
Failure to properly install the ow switch may result
in damage to the boiler/water heater heat exchanger
voiding the warranty!
Table 7 Temperature Rise Table
∆T = 15°F ∆T = 8.3°C
Model Flow Rate Pres. Drop Flow Rate Pres. Drop
Number GPM Ft L/s kPa
300 33.4 0.21 2.1 0.6
400 45.4 0.49 2.9 1.5
600 68.1 1.30 4.3 3.8
750 85.1 2.35 5.4 6.9
900 102.1 3.84 6.4 11.3
1050 119.1* 6.23 7.5 18.4
∆T = 20°F ∆T = 11.1°C
Model Flow Rate Pres. Drop Flow Rate Pres. Drop
Number GPM Ft L/s kPa
300 25.1 0.12 1.6 0.4
400 34.0 0.29 2.1 0.9
600 51.1 0.76 3.2 2.3
750 63.8 1.38 4.0 4.1
900 76.6 2.25 4.8 6.6
1050 89.4 3.66 5.6 10.8
1350 114.9* 7.17 7.2 21.1
∆T = 25°F ∆T = 13.9°C
Model Flow Rate Pres. Drop Flow Rate Pres. Drop
Number GPM Ft L/s kPa
300 20.0 0.08 1.3 0.2
400 27.2 0.19 1.7 0.6
600 40.8 0.51 2.6 1.5
750 51.0 0.91 3.2 2.7
900 61.3 1.49 3.9 4.4
1050 71.5 2.42 4.5 7.1
1350 91.9 4.74 5.8 14.0
1500 102.1 6.31 6.4 18.6
∆T = 30°F ∆T = 16.7°C
Model Flow Rate Pres. Drop Flow Rate Pres. Drop
Number GPM Ft L/s kPa
600 34.0 0.36 2.1 1.1
750 42.6 0.65 2.7 1.9
900 51.1 1.06 3.2 3.1
1050 59.6 1.73 3.8 5.1
1350 76.6 3.38 4.8 10.0
1500 85.1 4.50 5.4 13.3
1950 110.6* 9.20 7.0 27.1
2100 119.1* 11.27 7.5 33.2
∆T = 35°F ∆T = 19.4°C
Model Flow Rate Pres. Drop Flow Rate Pres. Drop
Number GPM Ft L/s kPa
750 36.5 0.49 2.3 1.4
900 43.8 0.80 2.8 2.4
1050 51.1 1.30 3.2 3.8
1350 65.6 2.54 4.1 7.5
1500 72.9 3.38 4.6 10.0
1950 94.8 6.91 6.0 20.4
2100 102.1 8.47 6.4 25.0
**Flow exceeds recommended maximum use a greater temperature
rise or consult manufacturer. Cupro-nickel heat exchanger should be
considered.