Finned copper tube gas boilers & water heaters – Boiler Manual
16
Figure 11 Typical Primary/Secondary Piping
(See Notes)
Figure 12 Low Temperature Piping with Thermostatic Valve
(See Notes)
H-1 Rev 4
NOTES:
1. Boiler circuit piping must be sized
large enough to handle maximum
ow through unit.
2. Boiler pump sized to boiler design
ow requirements.
3. All boilers furnished with factory
mounted outlet water temperature
gauge.
4. Boiler pump purging required.
Use terminals supplied.
Notice: These drawings show suggested pip-
ing conguration and valving.
Check with local codes and ordinances for
specic requirements.
H-18 Rev 3
NOTES:
1. For pump selection consult factory.
2. Boiler pump sized to boiler and thermostatic 3-way valve design ow
requirements.
3. Boiler circuit piping must be sized large enough to handle maximum ow
through unit.
4. All boilers furnished with factory mounted outlet water temperature gauge.
5. Boiler pump purging required. Use terminals supplied.
6. Valve is precalibrated for 140°F return temperature.
Notice: These drawings show suggested piping conguration and valving. Check
with local codes and ordinances for specic requirements.