DCN: 141-00240-02 7/03 6
SW1 Positions 5& 6: Thermal Equalizer Heat Run Time Mode Select
These two dipswitch positions determine the length of time that a Zone 1 Heat Call can be on before it times out
and is interrupted by an equalizer cycle.
OFF ON
5 Off Heat Run Time 8 Min
6 Off
5 On Heat Run Time 12 Min
6 Off
5 Off Heat Run Time 16 Min
6 On
5 On Heat Run Time 20 Min
6 On
SW1
FIG 5. DIPSWITCH SW1
EQUALIZER HEAT RUN TIME
SETTINGS
HRT1