EasyManua.ls Logo

RCS ZC2S - Configuration and Integration; HVAC System Wiring; Control Unit Setup: Dipswitch Settings

RCS ZC2S
7 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DCN: 141-00240-02 7/03 5
HVAC System Wiring
The ZC2S control units connect to the HVAC mechanical systems at the normal thermostat connections on the
HVAC indoor units.
WIRING FOR STANDARD HVAC SYSTEMS
Control Unit Setup: Dipswitch Settings
The control unit has a configuration dipswitch, SW1. Set the dipswitch as follows.
SW1 Position 1: Test Mode (For service technician use only, do not run in test mode)
Select OFF for Normal operation. All delays normal.
Select ON for Test mode to reduce delays to 10 seconds and shorten run times to one minute to facilitate
system checkout and troubleshooting.
SW1 Position 2: Fan Mode Select
Select OFF for Standard Gas systems (no fan with heat calls)
Select ON for Electric Heating systems (fan with heat calls)
SW1 Position 3& 4: Thermal Equalizer Mode Select
These two dipswitch positions determine the length of time the equalizer cycle will run after it has been tripped on
by the Heat Run Time timeout.
C 24VAC COM
R 24VAC
G FAN
W HEAT
Y COMP
R 24VAC
G FAN
W HEAT
Y COMPRESSOR
RED
GREEN
WHITE
YELLOW
INDOOR
FURNACE UNIT
OUTDOOR UNIT
“COMPRESSOR”
Y COMP
C 24VAC COM
ZONE CONTROL
UNIT
HVAC SYSTEM
Standard Thermostat
Wiring Color Codes
FIG 2. WIRING ZONE CONTROL UNIT TO STANDARD HVAC SYSTEM
OFF ON
3 Off: Equalizer feature Off.
4 Off
3 On Equalizer run time 6 Min
4 Off
3 Off Equalizer run time 8 Min
4 On
3 On Equalizer run time 10 Min
4 On
SW1
FIG 4. DIPSWITCH SW1
EQUALIZER RUN TIME
SETTINGS
ERT1
ERT2