WORK SAFE, READ THIS
Failure to read and comply with all warnings, cautions and instructions
prior to starting installation may cause personal injury and/or property damage
and void warranty.
Remove electrical shock hazard – DISCONNECT THE POWER BEFORE
INSTALLATION to avoid electrical shock and/or equipment damage. Do not use on
circuits exceeding 24 volts to avoid damage to switch, shock or re hazard.
NOTICENOTICE
In any installation where property damage and/or personal injury
might result from an inoperative switch, a back-up system(s) and/or alarm should
be installed.
NOTICENOTICE
The AquaGuard Drain pans and sensors must only be installed by a
licensed contractor or under the direct supervision of one. Condensation pan must
be properly maintained after installation and be kept free from foreign objects,
rust or other obstructions that might interfere with the proper operation of the
AquaGuard sensor. AG-4200E sensor/drain installation for Titan, Goliath and Goliath
Furnace drain pans.
STOP/READ
This device must be installed in accordance with manufacturer’s
instructions. This unit must be in accordance with all applicable local plumbing,
drainage and electrical codes.
INSTALLATION INSTRUCTIONS
AQUAGUARD
®
42
00E
Water Sensor & Drain Port
NOTICE
NOTICE
To ensure proper performance of product, instructions must be followed.
Wiring the AG-1250E:
Drain fitting and sensor installation
AG-1250E, AG-3150E, AG-3175E, AG-3180E, AG-4200E
STANDARD WIRING DIAGRAM
FOR BREAKING “WALL THERMOSTAT” POWER WIRE
1. In HVAC Unit locate HVAC Power wire going to “Wall Thermostat”, (Typically RED).
Break/Disconnect 24VAC Power wire going to “Wall Thermostat”.
A. Connect “RED”, “Input 24VAC (Hot)” and “Gray” “Common” wire of AG-1250E to 24VAC (Hot)
secondary side of 24VAC Transformer.
B. Connect “Purple”, “Normally Closed” wire of AG-1250E to Thermostat’s “R” Terminal wire.
NOTE: “Purple” wire must be connected to “Thermostat”. Maximum capacity 24VAC/5Amp.
C. Connect “BLACK”, “Input: 24VAC (Common)” wire of AG-1250E to 24VAC (COMMON) secondary
side of 24VAC Transformer or Thermostat’s “C”Terminal.
D. Optional: Connect “WHITE, “Normally Open” wire of AG-1250E to the “WHITE” wire of
AquaGuard, AG-9100 External Alarm or Home Alarm System, or Communicating System, etc...
If not used, wire nut and tape.
NOTE: “WHITE”, “Normally Open” wire maximum capacity, 24VAC/1Amp.
2. Test the AG-1250E Secondary Pan Sensor (At start-up check initial amperage load) while the HVAC
unit is on and functioning correctly. See installation sensor.
NOTE: When AG-1250E is wired correctly, the HVAC unit will shut off upon condensate detection.
the AG-1250E:
Moisture detection LED
Metal
contacts
C
o
m
m
o
n
-
G
R
A
Y
C
o
m
ú
n
-
G
R
I
S
T
r
a
n
s
f
o
r
m
e
r
H
o
t
R
e
d
24 VAC
(Hot)
24 VAC
(Common)
*Note:
Probe Wire Not Included
On Model AG-1250E
COMPRESSOR
AG-1250E, AG-3150E, AG-3175E, AG-3180E, AG-4200E
OPTIONAL WIRING DIAGRAM
FOR BREAKING COMPRESSOR WIRE
AG-1250E, AG-3150E, AG-3175E, AG-3180E, AG-4200E
FOR CONNECTING TO SENSOR PORT
(A) NORMALLY CLOSED SIGNAL
1. In HVAC Unit locate Compressor wire going to “Wall Thermostat”, (Typically YELLOW).
Break/Disconnect Compressor wire going to “Wall Thermostat”.
A. Connect typically “YELLOW” wire, going to “Wall Thermostat” to “Gray” “Common” wires of
AG-1250E.
B. Connect “Purple”, “Normally Closed” wire of AG-1250E to Compressor’s typically “YELLOW
wire going to compressor.
NOTE: “Purple” wire must be connected to Compressor “YELLOW” wire. Maximum capacity
24VAC/5Amp.
C. Connect “RED”, “Input: 24VAC (HOT)” wire of AG-1250E to 24VAC (HOT) of 2 VAC Transformer or
Thermostat’s “R”Terminal.
D. Connect “BLACK”, “Input: 24VAC (Common) wire of AG-1250E to 24VAC (Common) secondary
side of 24VAC Transformer or Thermostat’s “C” terminal.
E. Optional: Connect “WHITE”, “Normally Open” wire of AG-1250E to the “WHITE” wire of
AquaGuard, AG-9100 External Alarm (see Figure 1.) or Home Alarm System, or Communicating
System, etc... If not used, wire nut and tape.
NOTE: “WHITE”, “Normally Open” wire maximum capacity, 24VAC/1Amp.
2. Test the AG-1250E Secondary Pan Sensor (At start-up check initial amperage load) while the HVAC
unit is on and functioning correctly. See installation sensor.
NOTE: When the AG-1250E is wired correctly, (ONLY) the Compressor unit will shut-off upon
condensate detection. Air Handler will continue to run.
Page 1 of 2
1. Remove the threaded nut from the drain housing/ sensor carrier. (g. 1)
rubber gasket
thread nut
drain housing
sensor
(g. 1)
2. Install the drain housing from inside the pan MAKING SURE THE RUBBER GASKET
IS ON THE INSIDE OF THE PAN. (g. 2)
3. Screw the nut onto the drain housing from outside the pan and securely hand tighten. (g. 3)
4. Place the WARNING sticker on HVAC unit in a clearly visible location.
Question and Answer IconNeed help?

Do you have a question about the RectorSeal AQUAGUARD 4200E and is the answer not in the manual?

Summary

General Safety and Installation Warnings

Electrical Safety and Power Disconnection

Emphasizes disconnecting power before installation to prevent shock.

Contractor and Maintenance Requirements

Notes licensed contractor installation and regular pan maintenance.

Compliance with Codes

Mandates installation according to local plumbing and electrical codes.

Wiring the AG-1250 E

Standard Wiring Diagram: Thermostat Power Break

Guides wiring for breaking the thermostat's 24VAC power wire.

Optional Wiring Diagram: Compressor Wire Break

Guides wiring for breaking the compressor wire.

Sensor Port Connections

Details connecting AG-1250E to sensor port for NC and NO signals.

Drain Fitting and Sensor Installation

Physical Installation and Testing Procedure

Covers drain housing, sensor installation, and initial testing steps.

Drain Pan Installation Guidelines

Titan Drain Pan Installation

Instructions for installing the Titan drain pan, including support methods.

Goliath Furnace Horizontal Drain Pan Installation

Installation for Goliath Furnace horizontal drain pans with isolators.

Goliath Horizontal Drain Pan Installation

Installation for Goliath horizontal drain pans, including hanging options.

Goliath Furnace Vertical Drain Pan Installation

Installation for Goliath Furnace vertical drain pans with isolators.

Product Specifications and Warranty

Electrical Specifications Overview

Details relay contact ratings and voltage/ampere limits for the device.

Limited Warranty Terms

Outlines the terms and conditions of the product's limited warranty.

RectorSeal AQUAGUARD 4200E Specifications

General IconGeneral
ApplicationWater Leak Detection
Alarm Volume85 dB
Power Source9V Battery (Included)
Operating Temperature32° to 120°F (0° to 49°C)
Humidity Range0% to 95% non-condensing
Alarm TypeAudible alarm
Detection MethodConductivity
Cable Length6 feet (1.8 meters)