l
SIMPLE ON-LINE RANGE SETTING
(Using Actual Input Signal or Signal Generator)
l
USER SETTABLE FULL SCALE FREQUENCY FROM
1 Hz to 25 KHz
l
FOUR OUTPUT OPERATING RANGES
(0 to 5 V, 0 to 10 V, 0 to 20 mA, and 4 to 20 mA)
l
PROGRAMMABLE INPUT CIRCUIT ACCEPTS OUTPUTS FROM A
VARIETY OF SENSORS
l
85 to 250 VAC and 9 to 32 VDC POWERED VERSIONS
AVAILABLE
l
LOW FREQUENCY CUT-OUT AND OVERRANGE INDICATION
l
3-WAY ELECTRICAL ISOLATION (POWER/INPUT/OUTPUT)
l
INPUT AND OUTPUT INDICATION LED’s
MODEL IFMA - DIN-RAIL FREQUENCY TO ANALOG CONVERTER
DESCRIPTION
The Model IFMA accepts a frequency input, and outputs an analog voltage
or current in proportion to the input frequency, with 0.1% accuracy. The full
scale input frequency can be set to any value from 1 Hz to 25 KHz, either with
a frequency source, or digitally with the on-board rotary switch and push-
button.
The IFMA utilizes a seven position DIP switch, a rotary switch, a push button
and two indication LED’s to accomplish input circuit configuration, operational
parameter set-up, and Input/Output indication. The input circuitry is DIP switch
selectable for a variety of sources.
The indication LED’s are used during normal operation to display the input
and output status of the IFMA. These LED’s are also used to provide visual
feedback to the user of the existing parameter settings during parameter set-up.
The IFMA operates in one of four output modes. The programmable
minimum and maximum response times provide optimal response at any input
frequency.
The unit is equipped with a universal mounting foot for attachment to
standard DIN style mounting rails, including top hat profile rail according to EN
50 022 - 35 x7.5 and 35 x 15, and G profile rail according to EN 50 035 - G 32.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the
manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
SPECIFICATIONS
1. POWER:
AC Operation: 85 to 250 VAC, 48 to 62 Hz; 6.5 VA
DC Operation: 9 to 32 VDC; 2.5 W
Power Up Current: Ip = 600 mA for 50 msec. max.
2. SENSOR POWER: (AC version only) +12 VDC ±25% @ 60 mA max.
3. OPERATING FREQUENCY RANGE:
From 0 Hz to 25 KHz; user selectable.
4. SIGNAL INPUT: DIP switch selectable to accept signals from a variety of
sources, including switch contacts, outputs from CMOS or TTL circuits,
magnetic pickups, and all standard RLC sensors.
Current Sourcing: Internal 1 KW pull-down resistor for sensors with current
sourcing output. (Max. sensor output current = 12 mA @ 12 V output.)
Current Sinking: Internal 3.9 KW pull-up resistor for sensors with current
sinking output. (Max. sensor current = 3 mA.)
Low Bias: Input trigger levels V
IL
= 0.25 V, V
IH
= 0.75 V; for increased
sensitivity when used with magnetic pickups.
Hi Bias: Input trigger levels V
IL
= 2.5 V, V
IH
= 3.0 V; for logic level signals.
Max. Input Signal: ±90 V; 2.75 mA max. (With both Current Sourcing and
Current Sinking resistors switched off.)
5. SIGNAL VOLTAGE OUTPUT (Selectable):
0 to 5 VDC @ 10 mA max.
0 to 10 VDC @ 10 mA max.
6. SIGNAL CURRENT OUTPUT (Selectable):
0 to 20 mA @ 10 VDC min.
4 to 20 mA@ 10 VDC min.
7. OUTPUT COMPLIANCE:
Voltage: 10 V across a min. 1KW load (10 mA). Factory calibrated for loads
greater than 1 MW.
Current: 20 mA through a max. 500W load (10 VDC).
8. ACCURACY: ±0.1% of full scale range (±0.2% for 0 to 5 VDC range).
DIMENSIONS “In inches (mm)”
ORDERING INFORMATION
For more information on Pricing, Enclosures & Panel Mount Kits refer
to the RLC Catalog or contact your local RLC distributor.
IFMA0065IFMA0035
Pulse Rate to
Analog Converter
IFMA
85 to 250 VAC9 to 32 VDC
PART NUMBERS FOR AVAILABLE
SUPPLY VOLTAGES
DESCRIPTIONMODEL NO.
and UL Recognized Component,
File #E137808
R
R
C
INTERNATIONAL HEADQUARTERS EUROPEAN HEADQUARTERS
20 Willow Springs Circle, York, Pa. 17402, (717) 767-6511 FAX: (717) 764-0839 892 Plymouth Road, Slough, Berkshire SL1 4LP
Web site- http://www.redlion-controls.com E-mail- sales@redlion-controls.com ENGLAND +44 1753 696888 FAX: +44 1753 696339
RED LION CONTROLS
BULLETIN NO. IFMA-C
DRAWING NO. LP0340
REVISED 9/97
CAUTION: Read complete
instructions prior to installation
and operation of the unit.
CAUTION: Risk of electric shock.
Question and Answer IconNeed help?

Do you have a question about the Red Lion Controls IFMA and is the answer not in the manual?

Red Lion Controls IFMA Specifications

General IconGeneral
BrandRed Lion Controls
ModelIFMA
CategoryMedia Converter
LanguageEnglish

Summary

Product Overview and Specifications

Description

Provides a general overview of the IFMA's function and capabilities.

Specifications

Details technical parameters like power, frequency range, accuracy, and I/O.

Safety Summary

Outlines essential safety precautions for installation and operation.

Dimensions

Presents the physical size and mounting details of the converter.

Ordering Information

Lists part numbers for ordering different voltage versions of the IFMA.

Installation and Connection Guidelines

EMC Installation Guidelines

Provides methods to ensure compatibility and minimize interference in industrial environments.

Power and Output Connections

Details how to connect AC/DC power and output signals to the IFMA terminals.

Input Circuits and Configuration Setup

Sensor Input Circuits

Explains the input circuit configuration for various sensor types and signal levels.

Sensor Connection Examples

Illustrates wiring for different sensor types like magnetic pickups, proximity sensors, and TTL/CMOS.

Configuring the IFMA

Details how to set up the IFMA using DIP switches, rotary switch, and push button.

Output Indication and Operation Mode

Output Indication

Describes LED indicators for over-range, low frequency cut-out, and invalid entry states.

Operating Mode Selection

Explains how to select the analog output mode (voltage or current) using DIP switches.

Input Range and Response Time Settings

On-Line Input Range Setting

Describes setting the input range using an actual input signal or frequency generator.

Input Range Setting Using Rotary Switch

Details setting the input range manually using the rotary switch.

Minimum Response Time Setting

Explains how to configure the minimum time for output updates.

Advanced Settings and Calibration

Maximum Response Time Setting

Configures the low frequency cut-out response time for the unit.

Calibration

Details how to adjust minimum and full scale output values and set calibration direction.

Troubleshooting, Installation, and Application

Troubleshooting

Provides guidance for resolving common issues with the IFMA unit.

Installation

Explains how to physically mount the IFMA on standard DIN rails.

Application Example

Demonstrates a practical use case for the IFMA in a flow rate system.