5
Effective 06 2020 Drawing No. LP1155
DA50A Web User Interface
1. Connect a PC to the DA50A Gateway using an Ethernet cable
to Ethernet port 2 on the Gateway.
2. Set up the PC IP address by filling in the blank fields with the
information below:
Ethernet Port
IP Address 192.168.222.2
Subnet Mask 255.255.255.0
Default Gateway 192.168.222.1
Preferred DNS 192.168.222.1
3. Open a web browser and enter the following in the address
bar: https://192.168.222.222
4. To log in to the System webserver for the first time:
User Name: admin
Password: Refer to unique password located on unit
Note: For security, it is recommended to change the password
according to your company’s internal policy. To change the
password, go to AdministratorChange Password.
DA50A Cellular Connectivity
Cellular connectivity is achieved using the DA 4G LTE - CAT4/
CAT1 Modem Sled. Refer to the documentation shipped with
your DA 4G LTE - CAT4/CAT1 Modem Sled for installation and
setup information.
Ethernet Communications
Ethernet communications can be established at either 10
BASE-T or 100 BASE-TX. The DA50As RJ45 jack is wired as a
NIC (Network Interface Card). For example, when wiring to a hub
or switch use a straight-through cable, but when connecting to
another NIC use a crossover cable. Refer to the Crimson 3.2
Software Guide and Red Lion’s website for additional information
on Ethernet communications.
LED COLOR(S) MEANING
YELLOW solid Link established.
YELLOW flashing Data being transferred.
GREEN (OFF) 10 BASE-T Communications
GREEN (ON) 100 BASE-TX Communications
RS232 PORT
The DA50A has one
RS232 serial port that
can be used for either
programming or for
communications. The
RS232 port can be used
for either master or slave
protocols. The serial port
has a pair of LEDs to
indicate transmit and
receive activity. The
pinout is shown to the
right.
RS485/422 COMMS PORT
The RS485 port of the DA50A can be used for RS485 or RS422
communication. The serial port has a pair of LEDs to indicate
transmit and receive activity.
Note: All Red Lion devices connect A to A and B to B. Refer to
www.redlion.net for additional information.
Examples of RS485 2-Wire Connections
DH485 COMMUNICATIONS
The DA50A’s RS485/422 COMMS port can also be used for
Allen Bradley DH485 communications.
WARNING: DO NOT use a standard DH485 cable to connect
this port to Allen Bradley equipment. A cable and wiring
diagram are available from Red Lion at www.redlion.net/cables-
drivers.
STATUS RING LED
LED COLOR/STATE MEANING
Pulsating white PXE starting up
Steady dim white PXE running with Crimson stopped
Steady pale green PXE running with Crimson running
Steady pale red Accepted alarms present
Pulsating red Active Alarms present
Pulsating red and green Identify command received
Flashing red and white C3.2 crashed and restarting
WARNING - Do not connect or disconnect cables while
power is applied unless area is known to be non-hazardous.
Not hot swappable.
DA50A RS232 TO A PC
DA50A: RJ12 PC: DB9
Pin # Name Pin # Name
4 COMM 1 DCD
5 Tx 2 Rx
2 Rx 3 Tx
N/C 4 DTR
3 COMM 5 GND
N/C 6 DSR
1 CTS 7 RTS
6 RTS 8 CTS
N/C 9 RI
TX
5V
8
1
7
2
TxB
TxA
130K
130K
5
TxEN (OC)
RX
130K
5V
130K
RxB
4
RxA
3
COMM
6
TxEN (OC)
TX/RX
130K
5
TxA
2
8
130K
5V
7
1
TxB
6 COMM
RS485/422 4-WIRE
CONNECTIONS
RS485 2-WIRE CONNECTIONS
DA50A TO RED LION RJ11
DA50A : RJ45 RLC : RJ11
Pin # Name Pin # Name
5 TxEN 2 TxEN
6 COMM 3 COMM
1 TxB 5 B-
2 TxA 4 A+
DA50A TO MODULAR
CONTROLLER
DA50A Modular Controller
Pin # Name Pin # Name
1,4 TxB 1,4 TxB
4,1 RxB 4,1 RxB
2,3 TxA 2,3 TxA
3,2 RxA 3,2 RxA
5 TxEN 5 TxEN
6 COMM 6 COMM
7 TxB 7 TxB
8 TxA 8 TxA