Capacity
Specifications Powersupply: 120/240Vac,50/60Hz Autosensing
Powerconsumption: 16Wmax.,0.25Wwhenidle
Alarmrelay: 5A,30Vdc,250VacBreakonfault
Capacity: 12litres/hourmax.(3.17USgal/h)
Maximumhead: Vertical>20m(65ft),Horizontal>100m
(328ft)Suction1mmax.(3.28ft)
Ambienttemp: 0-40°C
Watertemp: 25°Cmax.
Material: Flameretardant ABSUL945VA
Dischargetube: 6mm(1/4”)ID
Dimensions: 286x61x53mm(11.3”x2.4”x2”)
IP: 44
TroubleShooting
Pumpdoesnotrun:
Pumpispumpingair:
Checkfuseandelectricalsupply
connections.
Checkthatwaterisreachingthepump
sensor.
Checkthatthecollectiontrayislevel.
Checkthatthesensoriscleanand
undamaged.
Checkthattheoutlettubeisnot
syphoning.
Pumpisnoisy:
Pumpcontinuestorunwithnowater:
Checkthatthemainscableandoutlettube
arenotvibratingagainstthesidesofthe
equipment.
Thesensormaybecontaminatedbydirt,
mouldorcertaincleaningchemicals.Gently
wipethesensorwithadampcloth.Ifthe
problempersists,repeatwithmethylated
spiritandthenrinsewithwater.