Controller
46
— English Fillcontrol Auto Make-up and degassing — 06.07.2016 - Rev. B
ER Code
Alarm
Floating
contact
Cause
Remedy
Alarm reset
07 Makeup cycles - Set value exceeded
• Check set value in the
Customer or Service
menu
• Seal the leak in the
system
Quit
08
Pressure
measurement
-
Controller receives incorrect
signal
• Connect the plug
• Check the cable for
damage
• Check the pressure
transducer
Quit
10 Maximum pressure - Set value exceeded
• Check set value in the
Customer or Service
menu
• Set the tripping
pressure of the safety
valve
-
11 Back-up volume -
"With water meter" must be
activated in the Customer menu
• Set value exceeded
• Severe water loss in the
system
• Check set value in the
Customer or Service
menu
• Check the water loss in
the plant system
Quit
15 Makeup valve -
Contact water meter measures
without makeup request
Check the motor ball valve
for leaks
Quit
16 Power failure - No power Connect to power -
19
Stop ˃ 4 hours
-
Device is in Stop mode for more
than 4 hours
Set the controller to
Automatic mode
-
20
Maximum makeup
quantity
- Set value exceeded
Reset the "Makeup quantity"
meter in the Customer menu
Quit
21
Maintenance
recommendation
- Set value exceeded Carry out maintenance Quit
30 I/O module fault - • I/O module defective
• Connection between option
card and controller faulty
• Option card defective
• Replace the I/O module
• Check the connection
between option card
and controller
• Replace the option card
-