2.11 Trouble shooting
COMPRESSOR INTERNAL PROTECTIONS SWITCH ON
Temporary loss of a power supply phase
Wait for automatic protection switch on
Use the proper power supply
Excessive ambient temperature
Obstructed heat exchangers
Clean the exchanger according to the maintenance
procedure
HIGH/LOW PRESSURE CONTROL SWITCH ON
Check electrical circuit/connections
Clean the exchanger according to the maintenance
procedure
Remove possible obstructions
Not enough refrigerant fluid
Contact a certified technician
Excessive ambient temperature
THE COMPRESSOR NEVER STOPS
Conditioned room with open doors/windows
Not enough refrigerant fluid charge
Contact a certified technician
THE COMPRESSOR NEVER STARTS
Not enough refrigerant fluid charge
Contact a certified technician
Wrong set-point of the working thermostat
Electrical circuit failure
Verify the power supply and the integrity of the fuses
Wait for an higher temperature
Verify air canals circuit
Verify air flow after defrost