1. Read these and all related instructions thoroughly and follow
them carefully.
2. Make certain all required safety equipment is in place and
operational.
3. Whether it is required or not, a gas mask (DEMAND TYPE AIR
PACK) should be available in the immediate area of the gas
feed equipment and all operating personnel should be properly
trained in its use. OPERATORS SHOULD NOT ENTER
AREAS WHERE CHLORINE EXISTS, UNESCORTED.
4. Chlorine, Sulfur Dioxide, and Ammonia gas or the fumes from
C
hlorine, Sulfur Dioxide, and Ammonia solutions can be lethal
in large enough doses. Always have a coworker observe from
a safe location when you are working on any part or component
of the gas feed system.
5. Avoid breathing the gas fumes of Chlorine, Sulfur Dioxide, and
Ammonia solutions and AVOID contact with your skin. Work
only in a well ventilated area.
6. Before working on the gas feed system, make certain that the
cylinder/container/manifold valve(s) are shut off. If the
cylinder/container/manifold valve(s) seem to be shut off, open
them one quarter turn, and immediately close them again to
make certain they are not frozen in the open position. If you
cannot turn the valve(s) in either direction, ALWAYS ASSUME
THEY ARE OPEN, and call your chemical supplier.
7. Do not use wrenches larger than the standard cylinder/container
wrench (approximately 8˝ long) and DO NOT hit the wrench
with a heavy object to open or close the valve.
8. Do not reuse lead gaskets. They may not seal properly thereby
permitting the release of gas.
9. Use only lead gaskets. Other types may contract with
temperature variations resulting in the escape of gas.
10.Check for gas leaks every time the vacuum regulator(s) are
connected or remounted onto the cylinder/container/manifold
valve.
11. The rate valve IS NOT a shut-off valve. To shut off the gas
supply, CLOSE THE CYLINDER/CONTAINER/MANIFOLD
VALVE(S).
PRECAUTIONS FOR PERSONAL AND SYSTEM PROTECTION
IMPORTANT:
Please mail or fax this registration form
to establish your warranty.
REGAL REGISTRATION CARD
IMPORTANT: To further establish your warranty and to enable us to contact you should the
need arise, please fill out this card and return it promptly. Please do it now. Thank you.
Chlorinators Incorporated, Stuart, FL is the only authorized Warranty Repair facility for
REGAL GAS DETECTORS/SMARTVALVES.
PLEASE PRINT, THANK YOU
Gas Detector/SMARTVALVE Serial No.(s)* 1._________________ 2._________________
*Serial No. plate located inside unit on the right
Purchased From __________________________________________________________
Your Name ____________________________________________ Title_______________
Organization ______________________________________________________________
Mailing Address ___________________________________________________________
City _____________________________________ State _____________ Zip ___________
Phone (__________) _____________________________________ Ext. ____________
REGAL Registration Card