OPERATING AND MAINTENANCE MANUAL
W
ASSERKÜHLER
BEDIENUNGS- UND WARTUNGSANLEITUNG

Table of Contents

Questions and Answers

  • L
    Lisa BushAug 17, 2025
    Why is the Rehsler Kuhlsysteme Chiller tank water outlet temperature too high?
    • K
      Kristin WilcoxAug 18, 2025
      The tank water outlet temperature might be higher than expected due to several reasons: * The thermal load might be too high. Try restoring the thermal load to within the preset limits. * The ambient temperature may be too high. If installed in a closed space, increase the air flow to lower the ambient temperature. * The condenser fins could be dirty. Clean the condenser fins. * The front surface of the condenser might be obstructed. Clear any obstructions. * There might be a refrigerant leak. In this case, a technician should check for leaks, eliminate them, and refill the unit. * The compressor protection may be tripping. If so, a technician should check for leaks, eliminate them, and refill the unit.
  • V
    Victoria FrenchAug 20, 2025
    What to do if Rehsler Kuhlsysteme TAE K20 displays high pressure switch tripped (HP) Alarm A01?
    • J
      janetmartinAug 20, 2025
      If the high pressure switch has tripped and Alarm A01 is displayed, consider the following possible causes: * The fan might not be working. Repair or replace the fan and verify its heat protection. * The ambient air temperature could be too high. Reduce the ambient temperature by increasing local ventilation. * Warm air might be recirculating due to incorrect installation. Change the unit's position or remove obstructions to prevent recirculation. * The condenser fins could be dirty. Clean the condenser fins. * The front surface of the condenser might be obstructed. Clean the front surface of the condenser. * The thermal load might be too high. Reduce the thermal load if possible.
  • E
    Eric WhiteheadAug 22, 2025
    What to do if Rehsler Kuhlsysteme TAE K20 Chiller compressor protection trips and Alarm A09 or A10 appears?
    • K
      Kenneth RamirezAug 22, 2025
      If the compressor protection trips and Alarm A09 or A10 is displayed, it could be due to: * A thermal load that is too high combined with a shortage of refrigerant. In this case, call a qualified refrigeration engineer to check for leaks and replenish refrigerant charge. * The rotation direction of the scroll compressor being wrong (only on three-phase units). If so, invert two phases of the power supply.
  • M
    Mrs. Bethany OconnellAug 26, 2025
    What to do if Rehsler Kuhlsysteme TAE K20 Chiller displays Water differential pressure switch FLOW alarm A08?
    • B
      bevansAug 26, 2025
      If the water differential pressure switch FLOW alarm trips and A08 is displayed, check the following: * If installed, the filter upstream from the unit may be obstructed. Clean the upstream filter. * The pump might be defective or rotating in the wrong direction (for three-phase supplies). Check the pump's electrical supply and, if necessary, invert two phases. * If the unit lacks a hydraulic kit, the water inlet and outlet might be inverted. Invert the water inlet and outlet.
  • W
    walkerjacquelineAug 27, 2025
    How to fix low pressure drop at pump outlet in Rehsler Kuhlsysteme Chiller?
    • R
      Richard SmithAug 27, 2025
      A low pressure drop (water pressure) at the pump outlet may be caused by: * Water flow being too high or the pump working incorrectly (high flow, low discharge head, high absorption). Reduce water flow to within the preset limits, for example, by partially closing a pump outlet cock. Reset the pump thermal protection and check the electrical absorption. * The evaporator being obstructed by dirt transported by the utilization water. Depending on the type of dirt, clean the evaporator by running a detergent solution which is not aggressive for steel, aluminum, and copper, or run a high water flow against the stream. Consider installing a filter upstream from the unit.
  • C
    Cheryl WrightAug 30, 2025
    What to do if Rehsler Kuhlsysteme TAE K20 Chiller displays low pressure switch tripped (LP) Alarm A02?
    • A
      Angela CarrAug 30, 2025
      If the low pressure switch has tripped and Alarm A02 is displayed, the possible causes are: * Lack of refrigerant. Call a qualified refrigeration engineer to check for leaks and replenish the refrigerant charge. * The filter upstream from the unit is dirty, if installed. Clean or replace the water inlet filter, if installed.
  • P
    Patricia PierceSep 2, 2025
    What causes the Rehsler Kuhlsysteme TAE K20 Chiller digital display and LEDs to turn off?
    • C
      Cody JonesSep 2, 2025
      If the digital display and all LEDs are off on your Rehsler Kuhlsysteme Chiller, even when the main switch is on, it could be due to: * The auxiliary circuit fuse tripping. Check the causes of the fuse tripping and replace the fuse. * Abnormal power consumption by one or more of the control board components. Try turning the unit off and on again. If this doesn't solve the problem, contact the nearest service center.
  • A
    Alyssa SnowSep 4, 2025
    What to do if Rehsler Kuhlsysteme Chiller shows Alarm P1, P2, P3, P4?
    • D
      Devin GilmoreSep 4, 2025
      If Alarm P1, P2, P3, or P4 is displayed on your Rehsler Kuhlsysteme Chiller, it indicates that the BEWOT, BTWOT, or BAT1 probe is damaged. Check that the temperature probe is correctly connected to the control board terminals and that the cable is undamaged. If necessary, replace the probe.
  • A
    Adam BarnettSep 6, 2025
    How to resolve the Rehsler Kuhlsysteme TAE K20 Chiller Alarm A08 pump thermal protection?
    • S
      Stephanie HullSep 6, 2025
      If the Rehsler Kuhlsysteme Chiller shows Alarm A08 for pump thermal protection, it may be due to: * The pump's thermal protection device tripping because the water flow is too high. Reset the thermal protection device and increase the pressure drop in the hydraulic circuit, for example, by partially closing the pump output valve. * The grille through which the pump cooling air passes being obstructed. Reset the thermal protection device and free the grille. * The pump being defective. Reset the thermal protection device and replace the pump.
  • J
    John DavisSep 9, 2025
    What causes Alarm A04 on Rehsler Kuhlsysteme TAE K20 Chiller and how to fix it?
    • M
      Mr. Benjamin Phillips MDSep 9, 2025
      If your Rehsler Kuhlsysteme Chiller displays Alarm A04, it indicates a low water outlet temperature. This can be due to: * The value fixed by the parameter is lower than the one measured by the probe. Identify and remove the cause which provoked BTWOT temperature decreasing to a value lower than Ar03. * Too low water flow. Increase the water flow.

Summary

Safety

General Safety Precautions

Guidelines for personnel handling and maintaining the unit safely.

Operational Safety

Critical safety rules for operating the chiller unit.

Maintenance and Repair Safety

Safety protocols for performing maintenance and repair tasks.

Refrigerant Gas Safety

Information and hazards associated with R134a refrigerant gas.

Installation

Unit Positioning Guidelines

Recommendations for placing the unit in the installation location.

Hydraulic Connections

Instructions for connecting the unit to the water piping system.

Electronic Board

Other Components Setting

Operation and Maintenance

Automatic Unit Operation

Description of the chiller's completely automatic operating mode.

Maintenance Procedures

General guidelines and safety for performing maintenance tasks.

Scheduled Maintenance Tasks

A schedule outlining regular maintenance checks and actions.

Trouble Shooting

Tank Water Outlet Temperature Issues

Troubleshooting for high outlet temperature or incorrect water flow.

Low Pressure Drop at Pump Outlet

Diagnosing and resolving low water pressure issues at the pump.

Water Differential Pressure Switch Flow Alarm

Addressing the FLOW alarm (A08) related to pressure difference.

High Pressure Switch Tripped (HP)

Causes and remedies for the high-pressure alarm (A01).

Low Pressure Switch Tripped (LP)

Causes and remedies for the low-pressure alarm (A02).

Compressor Protection Trips

Troubleshooting for compressor thermal protection alarms (A09, A10).

No Display or Power Issues

Steps for when the digital display and LEDs are off.

Probe Alarms (P1, P2, P3, P4)

Resolving alarms related to probe issues (P1-P4, A04).

Pump Thermal Protection and Flow Issues

Troubleshooting pump thermal protection and flow alarms (A08).

Configuration and EEPROM Error Alarms

Addressing configuration errors (ACF) and EEPROM faults (EE).

Setting Tables

Alarms

Alarm Codes and Actions

Comprehensive list of alarm codes, meanings, causes, actions, and resets.

Rehsler Kuhlsysteme TAE K20 Specifications

General IconGeneral
BrandRehsler Kuhlsysteme
ModelTAE K20
CategoryChiller
LanguageEnglish