5.2 Fault:
Compressor will not start although there is low or no pressure in the compressed air tank (see the display on the compressed air tank pressure gauge
(Fig.4 (30)).
Cause:
Remedy:
Compressor emergency stop button (Fig.4 (29)) is switched off.
Switch on compressor by pulling out the emergency stop button.
REMS Multi-Push defective.
Have the REMS Multi-Push checked/repaired by an authorised REMS
customer service workshop.
5.3 Fault:
The necessary minimum fl ow velocity is not achieved in the fl ushing program.
Cause:
Remedy:
Stop tap of the house connection is only partly open.
Fully open the stop tap.
Fine fi lter (Fig. 3 (12)) is contaminated.
Clean or change the fi ne fi lter and fi lter cartridge.
Not enough tapping points opened.
Open the appropriate number of tapping points.
Hoses connected incorrectly.
Connect hoses as shown in Fig. 3.
Wrong defaults entered.
Check defaults, correct if necessary. Restart the program.
Valves blocked, considerable, irremovable encrustations in the pipes.
Clean/change valve(s). Clear encrustations.
5.4 Fault:
The set pressure (p refer) is not reached in the test with compressed air or compressed air pump programs
(REMS Multi-Push SL/SLW).
Cause:
Remedy:
Installation or compressed air hose (Fig. 4 (23)) leaking.
Check installation for leaks. Change the compressed air hose.
No or too little pressure in the compressed air tank.
See 5.2 Fault:
REMS Multi-Push defective.
Have the REMS Multi-Push checked/repaired by an authorised REMS
customer service workshop.
5.5 Fault:
The set pressure (p refer) is not established in the test with water program (Multi-Push SLW).
Cause:
Remedy:
The water pressure of the house connection is greater than the set pressure
(p refer).
Close the shut-off valve of the house connection.
Suction/pressure hose (Fig. 1 (13)) or high-pressure hose (Fig. 4 (26)) leaking.
Change suction/pressure hose or high-pressure hose.
Hydro-pneumatic pump does not build up pressure.
Connect suction/pressure hose between the house connection and the
pressure test with water supply, see 2.6.2.
Stop tap of the water supply is closed or only partly open.
Fully open the stop tap.
No or too little air pressure in the compressed air tank.
Hydro-pneumatic pump requires compressed air, see 5.2 Fault:
REMS Multi-Push defective.
Have the REMS Multi-Push checked/repaired by an authorised REMS
customer service workshop.
5.6
Fault:
The pressure in the pipe to be tested is not relieved after running the test with water programs or during the test with water B, P+M
(REMS Multi-Push SLW).
Cause:
Remedy:
Pressure relief water drain (Fig. 4 (27)) is soiled or defective.
Clean the pressure relief water drain or have it replaced by qualifi ed personnel
or an authorised REMS customer service workshop.
REMS Multi-Push defective.
Have the REMS Multi-Push checked/repaired by an authorised REMS
customer service workshop.
5.7 Fault:
No or not enough ingredient is injected from the bottle.
Cause:
Remedy:
Unsuitable disinfectant, cleaning, preserving agent.
Use REMS Peroxi Color, REMS CleanH, REMS NoCor.
REMS V-Jet TW or REMS V-Jet H connected wrongly to the Multi-Push.
Note the direction of fl ow arrow, see also 2.5.
REMS V-Jet TW or REMS V-Jet H soiled.
Clean REMS V-Jet TW or REMS V-Jet H, see also 4.1.
REMS V-Jet TW or REMS V-Jet H defective.
Wrong REMS V-Jet TW or REMS V-Jet H unit connected.
Have REMS V-Jet TW or REMS V-Jet H checked/repaired by authorised
REMS customer service workshop.
Use REMS V-Jet TW exclusively for REMS Peroxi Color.
Use REMS V-Jet H exclusively for REMS CleanH cleaner and REMS NoCor
corrosion protection.
5.8 Fault:
The date and time must be reset every time the
REMS Multi-Push
is switched on.
Cause:
Remedy:
Battery depleted.
Change battery. See 4.1.
5.9 Fault:
The new version software was not installed.
Cause:
Remedy:
USB stick not recognised.
Use another USB stick.
New version software is not on the USB stick.
Copy new version software to the USB stick.
The USB stick was pulled out of the USB port
(Fig. 2 (33)) during the installation.
Repeat the procedure described in 2.3.. Use a USB stick with a LED if
possible.
A folder was created on the USB stick and the new version software was
copied into this folder.
Move the new version software into the main directory of the USB stick.
5.10 Fault:
The fl ushing and testing programs have been incorrectly displayed on the PC.
Cause:
Remedy:
The font “Lucida Console” is required for a correct display.
Select font “Lucida Console”, install if necessary.
5.11 Fault:
Printing on paper weak or illegible. Printout aborted prematurely.
Cause:
Remedy:
Weak battery charge.
Charge battery.
Paper reel inserted incorrectly in printer.
Insert paper roll, see
3.8.
The printer can only be used as of Version Software 2.0.
Load software by USB stick as a download under www.rems.de → Downloads
→ Software into the controller of the REMS Multi-Push, see 2.3.
5.12 Fault:
“Error” is displayed on the screen (6).
Cause:
Remedy:
A fault has occurred.
Unplug REMS Multi-Push. Remove all hoses, caps and stoppers. Then restart
REMS Multi-Push. If “Error” still appears, have the REMS Multi-Push checked/
repaired by an authorised REMS customer service workshop.