INSTALLATION INSTRUCTIONS
69-2253EF-01
VR8215S,M,T Single Stage
Direct Ignition Gas Controls
APPLICATION
The VR8215S,M,T Single Stage Direct Ignition Gas
Controls are used in gas-fired appliances with up to
150 ft
3
/hr capacity at 1 in. wc pressure drop on natural
gas. They have been optimized for direct ignition
applications and include a on/off switch and a pressure
regulator.
Valve capacities are shown in Table 1.
Table 2 provides gas capacity conversion factors.
For suffix letter designation, see Table 3.
VR8215M valves are designed for agricultural
applications.
SPECIFICATIONS
Table 1. Valve Capacity.
a
a
Capacity based on 1000 Btu/ft
3
, 0.64 sp gr natural gas at 1 in. wc pressure drop (37.3 MJ/m
3
, 0.64 sp gr natural gas at 0.25 kPa pressure drop).
b
Minimum regulation for LP gas is 30,000 Btu/h (0.85 m
3
/hr).
Table 2. Gas Capacity Conversion Factor. Table 3. Model Number Suffix Letter Designation.
Options:
3/16 in. (4.8 mm) and 1/4 in. (6.4 mm) male quick-
connect ground terminals.
Barbed vent fittings for seated combustion:
Single stage: 1/8 in. (3.2 mm) and 1/4 in. (6.4 mm)
Body Pattern: Straight through; see Table 1 for inlet and
outlet size.
Electrical Ratings:
Voltage and Frequency: 24 Vac, 50/60 Hz.
Current Draw:
Single Stage: 0.5 A.
Field Wiring:
Single Stage: Two 1/4 in. spade quick-connect terminals.
Capacity: See Table 1.
Conversion:
Use conversion factors in Table 2 to convert capacities
for other gases.
Regulation Range: See Table 6.
Natural-LP Gas Conversion Kits: See Table 4.
Approvals:
CSA Design Certificate #112395.
(-40 °F to +175 °F; -40 °C to +79 °C)
Australian Gas Association Certificate #7960.
(single stage only) (-20 °C to +79 °C only)
Outlet: Class 2, Grade 20 pressure regulator
Auto shutoff valve function: Class 3
Table 4. Natural-LP Gas Conversion Kits.
Model
Size
Inlet x Outlet
(in. NPT)
AGA Certified Capacity for Natural
Gas
AGA Certified Minimum
Regulation for Natural Gas
AGA Certified
Maximum Regulation
for Natural Gas
ft
3
/hr m
3
/hr ft
3
/hr m
3
/hr ft
3
/hr m
3
/hr
VR8215 1/2 x 1/2 150 4.25
15
b
0.42 200 5.66
Gas Specific Gravity
Multiply Listed
Capacity By
Manufactured 0.60 0.516
Mixed 0.70 0.765
Propane 1.53 1.62
Regulation
Model Number
Suffix Letter
Pressure Regulator
Type
Single Stage
S, M Standard
T Slow Opening
Model Number Suffix Letter Kit to Convert Natural Gas to LP Kit to Convert LP to Natural Gas
S, M, T 396221 396222
Question and Answer IconNeed help?

Do you have a question about the resideo VR8215 and is the answer not in the manual?

Summary

Specifications

Installation Instructions

Installation

Instructions for installing the product, including safety warnings and technician requirements.

Install Control

Wiring

Startup and Checkout

Perform Gas Leak Test

Procedure for checking for gas leaks after any work on the gas system.

Gas Leak Test

Detailed steps for applying a soap and water solution to detect gas leaks at connections.

Check and Adjust Gas Input and Burner Ignition

Verifying gas input and burner ignition, including checks with a manometer or gas meter.

Check Safety Lockout

Check Safety Shutdown Performance

Service

If Main Burner Does Not Come On With Call For Heat

Troubleshooting steps for when the main burner fails to ignite during a call for heat.