CABINET LENGTHS
kW in. mm
2 to 6 28 711
8 to 12 48 1219
15 to 18 66 1676
20 to 24 80 2032
ATTENTION
Basic precautions should always be taken to reduce the risk of
re, electric shock, and injury.
- Read all instructions before using this heater.
- This heater is hot when in use. To avoid burns, do not let bare
skin touch hot surfaces. Keep combustible materials, like
furniture, pillows, bedding, papers, clothes, and curtains at least
48 in. (1219.2 mm) from the front of the heater.
- Do not use outdoors.
- Do not insert or allow foreign objects to enter any ventilation
or exhaust opening as this may cause an electric shock, re,
or damage the heater.
- Do not block air intakes or exhaust in any way whatsoever.
- A heater as hot and arcing or sparking parts inside. Do not use
in areas where gasoline, paint, or ammable liquids are used
or stored.
- Use this heater only as described in this manual. Any other use
not recommended by the manufacturer may cause re, electric
shock, or injury.
CAUTION
- Never install air outlet less than 24 in. (60 cm) from an
opposite surface and/or 12 in. (30 cm) from an adjacent
surface.
- Never install air inlet less than 6 in. (15 cm) of an opposite
surface.
- Disconnect all power supplies before working on any circuit.
- Install lters only if regular maintenance will be made. Do not
install lters in ceiling applications.
MAINTENANCE
Once a year, remove the front panel and use a vacuum cleaner to
remove the dust accumulation inside the heater.
Cleaning should be done while the heater is disconnected from the
supply circuit.
Any other servicing should be performed by a quali ed techni-
cian.
KEEP THIS INSTRUCTION PAMPHLET
FOR THE USER
INS136-200310-02
RECESS AND SEMI-RECESS MOUNTING
1- Unit must be installed with trim frame of appropriate length.
2- Provide an opening of 1 in. (2.5 cm) on length and height
greater than the size of the actual unit.
3- Remove front panel and open control section door.
4- Remove appropriate knockouts, secure supply and control
cables.
5- Secure trim frame to unit using the supplied metal piercing
screws.
6- Secure unit in place without warping using appropriate screws,
shim if required. For ceiling application, use 1/2 in. X 13 UNC
threaded rods.
7- Connect the unit according to local and national codes.
See wiring diagram on control section door.
8- Close control section door and put front panel in place.
9- Test unit by temporarily setting thermostat at maximum
temperature.
SUB-BASE MOUNTING
1- Unit must be installed on a sub-base of appropriate length.
2- Secure sub-base bracket to the oor.
3- Secure sub-base to unit using the supplied metal piercing
screws.
4- Remove front panel and open control section door.
5- Remove appropriate knockouts and secure supply and
control cables.
6- Secure unit and sub-base to sub-base bracket using the
supplied screws.
7- Follow steps 7 through 9 of recess mounting.
SURFACE MOUNTING
1- Run supply and control cables to the back of the unit.
2- Remove front panel and open control section door.
3- Remove appropriate knockouts, secure supply and control
cables and follow steps 6 through 9 of recess mounting.
MOUNTING APPLICATIONS
DIMENSIONS
mm
inches
THE INSTALLATION MUST BE EXECUTED
BY A QUALIFIED TECHNICIAN
RISK OF ELECTROCUTION
Reznor LLC
O’Fallon, MO USA 63368
Tel.: 1 800 695-1901
www.ReznorHVAC.com
©2014 Reznor, LLC. All rights reserved. All other trademarks are the
property of their respective organizations.
INSTRUCTIONS
EMC Model
Question and Answer IconNeed help?

Do you have a question about the Reznor EMC Series and is the answer not in the manual?

Reznor EMC Series Specifications

General IconGeneral
ThermostatOptional
TypeElectric Heater
Voltage208V, 240V, 480V
Phase1 or 3
ControlsBuilt-in or Remote
Heating Capacity5 - 50 kW
Control TypeThermostat

Summary

Product Overview and Safety Information

Model Identification and Installation Requirement

Identifies the EMC Model and states installation must be done by a qualified technician.

General Safety Precautions

Basic precautions to reduce risk of fire, electric shock, and injury, including hot surface warnings.

Installation and Usage Cautions

Cautions regarding air clearances for installation and warnings against improper usage.

Mounting Procedures

Recess and Semi-Recess Mounting

Step-by-step instructions for recess and semi-recess installation, including trim frame usage.

Sub-Base Mounting

Instructions for installing the unit on a sub-base, securing bracket and unit.

Surface Mounting

Steps for running cables and securing the unit for surface installation.

Mounting Applications and Diagrams

Wall Mounted Units

Illustrations of wall mounting configurations for up air flow and down air flow units.

Ceiling Mounted Units

Diagrams showing ceiling mounting types, including semi-recessed and recessed options.

Installation Configurations

Visual examples of recess trim kit, sub-base, and surface installation methods.

Maintenance and Servicing

Annual Maintenance

Procedure for cleaning dust accumulation inside the heater annually.

Professional Servicing

Statement that any other servicing should be performed by a qualified technician.