FIGURE 63
INTEGRATED FURNACE CONTROL (IFC) UTEC 1028-927 OR
JOHNSON CONTROLS G961DAJ-2401 (SPARK IGNITION)
55
CHECK FOR BLOCKED VENT
CHECK AIR PROVING SWITCH (CLOSED)
CHECK WIRING TO IGNITER
CHECK FOR SPARK AT IGNITER,
ELECTRODE
1. SET FAN SWITCH TO AUTO
2. SET THERMOSTAT TO CALL
FOR HEAT
START
NO
NO
YES
YES
YES
YES
YES
NO
INDUCED DRAFT BLOWER
MOTOR STARTS
YES
NO
SPARK IGNITER ENERGIZES
YES
30 SEC. PREPURGE
REPLACE (IFC)
NO
REPLACE SWITCH
NO
REPLACE (IFC)
IF WIRING TO
DRAFT MOTOR IS OK
NO
REPLACE SWITCH
NO
REPLACE (IFC)
IF WIRING TO
IGNITER IS OK
NO
CHECK THERMOSTAT
WIRING
CHECK LINE VOLTAGE POWER
CHECK LOW VOLTAGE TRANSFORMER
CHECK “IN-LINE” FUSE ON TRANSFORMER
LOW VOLTAGE LINE
INTEGRATED FURNACE CONTROL (IFC)
TROUBLESHOOTING GUIDE
(SPARK IGNITION SYSTEM)
POWER LED ON
IF THE PRESSURE SWITCH DOESN’T
CLOSE WITHIN 60 SEC. THE IOM WILL
STOP FOR 5 MIN. AND RETRY
REMOVE (IFC) COVER, CHECK LIGHTS
MICROPROCESSOR STATUS LED ON
NOTE: “OK” LED WILL FLASH TO INDICATE
TWINNING CIRCUIT FAULTS
CHECK FOR 115VAC TO DRAFT MOTOR
REPLACE DRAFT MOTOR
CHECK FOR 24 VAC FROM
“W” TO “C” ON IFC
CHECK LIMITS, (CLOSED)
CHECK WIRING
CHECK PRESSURE SWITCH, (OPEN)
YES
REPLACE IGNITER
NOTE:
STATIC DISCHARGE CAN DAMAGE INTEGRATED FURNACE CONTROL (IFC)
WARNING
DISCONNECT POWER BEFORE
SERVICING.
SERVICE MUST BE BY A TRAINED,
QUALIFIED SERVICE TECHNICIAN.
HAZARDOUS VOLTAGE
LINE VOLTAGE
CONNECTIONS CAN
CAUSE PERSONAL
INJURY OR DEATH

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rheem RGTA SERIES and is the answer not in the manual?

Rheem RGTA SERIES Specifications

General IconGeneral
BrandRheem
ModelRGTA SERIES
CategoryFurnace
LanguageEnglish

Related product manuals