SAMPLE HYDRONIC AIR HANDLER PERFORMANCE
WATER INLET
TEMP (°F) [°C]
WATER OUTLET
TEMP (°F) [°C]
WATER FLOW
AIR INLET
TEMP (°F) [°C]
AIR OUTLET
TEMP (°F) [°C]
CAPACITY
(BTU/HR) [kW]
AIR TEMP
RISE (°F) [°C]
120 [49] 110 [43] 106 [41] 20900 [6.13] 30 [17]
130 [54] 117 [47] 113 [45] 25800 [7.56] 37 [21]
140 [60] 125 [52] 122 [50] 29800 [8.73] 43 [24]
150* [66] 132 [56] 130 [54] 35000 [10.26] 50 [28]
160 [71] 140 [60] 137 [58] 40000 [11.72] 57 [32]
120 [49] 100 [38] 105 [41] 38200 [11.20] 31 [17]
130 [54] 108 [42] 109 [43] 44900 [13.16] 37 [21]
140 [60] 115 [46] 116 [47] 50600 [14.83] 42 [23]
150 [66] 120 [49] 126 [52] 60000 [17.58] 49 [27]
160 [71] 126 [52] 129 [54] 67100 [19.67] 55 [31]
120 [49] 106 [36] 103 [39] 45500 [13.33] 26 [14]
130 [54] 113 [39] 108 [42] 53700 [15.74] 31 [17]
140 [60] 121 [43] 113 [45] 62500 [18.32] 36 [20]
150 [66] 128 [46] 120 [49] 71800 [21.04] 42 [23]
160 [71] 135 [49] 123 [51] 80500 [23.59] 47 [26]
120 [49] 96 [36] 100 [38] 47200 [13.83] 27 [15]
130 [54] 101 [38] 110 [43] 57800 [16.94] 33 [18]
140 [60] 106 [41] 112 [44] 66900 [19.61] 38 [21]
150 [66] 111 [44] 119 [48] 77000 [22.57] 44 [24]
160 [71] 106 [46] 124 [51] 86800 [25.44] 50 [28]
AIR CFM
[L/s]
LB/HR
GPM
CFM - Cubic Feet Per Minute
Performance is based on the following assumptions:
1) an estimated 100 ft. [30m] equivalent length of 0.75-inch piping
2) 0.50” [13] w.c. of external air static.
SAMPLE HYDRONIC AIR HANDLER PERFORMANCE
646 [305]
1000 [462]
1450 [684]
1800 [850]
68 [20]
68 [20]
68 [20]
68 [20]
[kg/hr]
2000/
[907]
2000/
[907]
2000/
[907]
2000/
[907]
4
4
4
4
RHWB-04WMP36A
RHWB-04WMX36A
RHWB-06WMP48A
RHWB-06WMX48A
RHWB-08WRP60A
RHWB-08WRX60A
RHWB-10WRP60A
RHWB-10WRX60A