MLM WIRELESS WALL THERMOSTAT
RICKARD 2018
HARDWARE LAYOUT
Up to 50m RF Comms Radius
Max: 15 Wall Stats/AP
One Access Point per PSU unit.
15 Diffusers Maximum/PSU
RF WALL THERMOSTAT
RF WALL THERMOSTAT
ACCESS POINT (AP)
POWER SUPPLY UNIT (PSU)
VAV DIFFUSER
RF WALL THERMOSTAT
 Accurately senses and sets room temperature.
 Converts any Slave diffuser into a Master so that it can con-
trol a zone of up to 15 diffusers.
 Compatible with MLM and MLC systems.
SELECTION
Use when individual temperature control is a requirement.
Use when flexibility and sensing accuracy is a priority.
Use to reduce the cost of a Wall Thermostats Installation.
Use when stratification in heating is a problem.
SPECS
 RF frequency 868MHz ISM band
 Max TX level 10dbm
 Receive level up to -100dbm
 Encoding 2-GFSK
 Communication rate 38 kBaud
 Battery 2 x 1.5V AAA Lithium cell
 Battery life 3 to 5 years.
 Battery low voltage indication (< 2.8V)
 RSSI RF signal strength indication (RSSI low at < -85 dbm)
 Selectable setpoint/RTC/Room temperature display
 Info display – Battery Voltage or RSSI display.