Programmable Relay ● User Manual for ELC, EXM and PR Series 140 2020 v6.0 ● © Rievtech Co.,
Ltd. ● www.rievtech.com
PV = (analog value on
input * gain) + offset.
You can connect the input
for example by means of an
analogue input with a
PT100 sensor.
The gain parameter
influences PV
The offset parameter
influences PV
PV is restricted by the
parameters Min. and Max.
In each
case: -
10,000 to
+20,000
The Dir parameter gives the
action direction of the
controller.
Positive means: If the set
value > process value then
the process value is
increased; if the set value <
process value then the
process value is reduced.
Negative means: If the set
value > process value then
the process value is
reduced; if the set value <
process value then the
process value is increased.
e.g. heat regulation: if the
set value is greater than the
process value (room is too
cold), the manipulated
variable increases the
process value.
Analogue Ramp
Description of function
The Analogue Ramp instruction allows the output to be
changed from the current level to a selected level at a
specified rate.
A change in the status from 0 to 1
at input EN (Enable) applies the
start/stop level (Offset "B" + StSp) to
the output for 100 ms and starts the
ramp operation to the selected level.
A change in the status from 1 to 0
immediately sets the current level to
Offset "B", which makes output AQ
equal to 0.
SeI = 0: The step 1 (level 1) is
selected.
SeI = 1: The step 2 (level 2) is
selected.
A change in the status of Sel
causes the current level to start
changing to the selected level at
the specified rate.
A change in the status from 0 to 1
at input St (Decelerated Stop)
causes the current level to decrease
at a constant rate until the
start/stop level (Offset "B" + StSp)
is reached. The start/stop level is
maintained for 100 ms and then
the current level is set to Offset "B",
which makes output AQ equal to 0.
Level1 and Level2: Levels to be
reached; value range for each level:
-10,000 to +20,000
MaxL: a Maximum value that must
not be exceeded.
Value range: -10,000 to +20,000
StSp: Start/Stop offset value that is
added to Offset "B" to create the
start/stop level. If the Start/Stop
offset is 0, then the start/stop level
is Offset "B").
Value range: 0 to +20,000