EasyManua.ls Logo

Rievtech ELC Series - Page 167

Rievtech ELC Series
355 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EN
Programmable Relay User Manual for ELC, EXM and PR Series 167 2020 v6.0 © Rievtech Co.,
Ltd. www.rievtech.com
Parameter
Slave address: 1 is a default.
Communication protocol: Modbus
(RTU)
Communication parameter: baud
rate (BPS), Data bits, Stop bits,
Parity, Overtime (response timeout)
Comm Type: RS232 or
RS485(Communication interface of
xLogic)
Data register Index: High Low /Low
High
Command:
01 Read coils(0x)
02 Read Discrete Input(1x)
03 Read Holding Registers(4x)
04 Read Input Registers(3x)
Register start address, count
Output Q
Q is set or reset depending on the
communication status.
Successful communication, Q=1;
Failed communication, Q=0;
NOTICE:
Data register Index: High Low /Low High
For example, when the HighLow index is set, and the
data 0x0012 was read and saved to AQ, then AQ=
0X0012; however, when the LowHigh index is set, then
AQ= 0x1200.
Refer to the Modbus RTU Communication Manual for
more information.
Description of the function:
In the configuration of our xLogic communication, the
xLogic usually serves as a slave via Modbus RTU Protocol
and can communicate with a master directly. That’s to say,
any device communicating with xLogic sends a command
to it, and then its response will be sent out only when the
xLogic has received the command, just as the below figure
shows:
However, the “Modbus Read” or “Modbus Write” (see next
chapter) function blocks should be used if xLogic shall be
required to play a role of master to communicate with
other slave devices. As the following figure shows:
When you put the “Modbus read” or “Modbus Write”
function block in your program the xLogic CPU will behave
as a Modbus RTU Master.

Related product manuals