EasyManua.ls Logo

Rievtech ELC Series - Page 172

Rievtech ELC Series
355 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EN
Programmable Relay User Manual for ELC, EXM and PR Series 172 2020 v6.0 © Rievtech Co.,
Ltd. www.rievtech.com
Write the I2 bit status of Master xLogic to Slave No1
xLogic and control Q1 of the slave via RS485 port. The
program of a master would be as follows:
I1 of the master is used to control the communication. If
I1 is high and the communication is established
successfully, one alarm message (text message block) will
be displayed on the LCD. Then Q1 of slave No.1 will be
controlled by I2 of the master. If I2 is high, Q1 of slave
No.1 would be ON and if I2 is low, Q1 of the slave would
be OFF.
NOTICE:
The Q1 of the Slave must be free No other
blocks can be connected to its input pin.
Example 2, manual mode input value
The above configuration is to force Q1, Q2, Q3 of Slave
No.1 ON. "means pre-set the BIT 1 and
"means pre-set the BIT 0 ”Coil 0” is
corresponding to the start address, Here it is Q1.
NOTICE:
The manual input value is Hex data .it contains 4
bytes. If you want to write a decimal value to the register
of the slave, it must be converted to Hex format first.
4. The following table shows how to set each output.
Note: This table also applies to the Modbus Read function
block
Model
I, Q, AI, AQ
Dialog box set
CPU
I1-IC
I1-I12
Q1-Q6
Q1-Q6
AI1AI8
AI1AI8
AQ1AQ2
AQ1AQ2
Expansion1
(Address is 1)
I11-I18
I13-I20
Q11-Q18
Q7-Q14
AI11-AI18
AI9AI12
AQ11-AQ12
AQ3, AQ4
Expansion2
(Address is 2
I21-I28
I21I28
Q21-Q28
Q15Q22
AI21-AI28
AI17---AI24
AQ21-AQ22
AQ5--AQ6
…………….

Related product manuals