EasyManua.ls Logo

Rievtech ELC Series - Page 174

Rievtech ELC Series
355 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EN
Programmable Relay User Manual for ELC, EXM and PR Series 174 2020 v6.0 © Rievtech Co.,
Ltd. www.rievtech.com
Modbus Read Write
Description of function
This function block is for Ethernet PLC which have a built-
in webserver. This block is used when the CPU is to act as
a Modbus Master (Client).
If the CPU does not have a built-in webserver, then please
use the standard Modbus Read and Modbus Write blocks
above.
When activated by a high signal on the En pin, this block
will enable the CPU to communicate via RS232 or RS485
or Ethernet as a Modbus Master (Client). If the connection
to the Slave (Server) device is established, then the output
pin of this block will be set high.
Connection
Description
Input En
A high signal at the En input will
enable the Modbus Read Write
block to be activated.
Input R
Resets the block with a high signal
on the R pin. The CPU will be
disconnected from the Slave. Input
R has priority over input En.
Parameter 1
Communicate Parameters
Comm Type:
o Com 0 (RS232 or PRO485)
o Com 1 (Expansion RS485)
o Com 2 (Built-in RS485
o Ethernet (Channels 1 to 8)
Com 0, 1 or 2 Settings:
o BPS: Baud Rate
o Data Bits: 5, 6, 7 or 8
o Stop Bits: 1, 1.5 or 2
o Parity Bit: None, Odd, Even,
Mark or Space
Ethernet Settings:
o Remote: 1 to 8
o Local CPU: Client
(Master) or Server
(Slave)
Protocol:
o Modbus RTU or
Modbus/TCP
Timeout: Connection timeout in
seconds.
TCP/UDP: Use TCP or UDP
Modbus Type: Standard or
Custom (See Parameter 2
below)
Slave Address: Default is 1
Data Register Index: High/Low
or Low/High (Word Swapped)
Command (Modbus Function):
o 01 Read Coil (0x)
o 02 Read Discrete Input (1x)
o 03 Read Input Registers (4x)
o 04 Read Holding Registers
(3x)
o 15 Write Multiple Coil
o 16 Write Multiple Registers
Register Address: Start register
Count: Number of registers
Auto:
o For Modbus Commands 01
and 02, options are:
Q Physical outputs
F Digital Flags
o For Modbus Command 03,
options are:
AF- Analogue flags

Related product manuals