Current Transformer Primary value Edit
Pressing the key will scroll the value of the most significant digit.
position and advances the cursor to the next Less significant digit.
When the least significant digit has been set, pressing the “
key will advance to the “Current transformer Primary Value
Pressing the “ ” key accepts the present value at the cursor
confirmation” screen. When CT primary is set less than 1A
X1000
L1
L2
L3
V
X1000
L1
L2
L3
A
RMS
TRUE
, then meter shows “Err” and CT primary is set to 1A.
minimum CT primary value that user can set is 1A.
Note : the flashing decimal point indicates the cursor position, a steady decimal point will be
present to identify the scaling of the number until the cursor position coincides with the steady
decimal point position. At this stage the decimal point will be flashing.
Current Transformer Primary Value Confirmation
This screen will only appear following an edit of the Current
Transformer Primary Value.
If the set value is to be corrected, pressing the “ ” key will
return to the “Current Transformer Primary Value Edit” stage.
Pressing the “ ” key sets the value and then advance to the
“CT secondarySelection menu.
X1000
L1
L2
L3
V
X1000
L1
L2
L3
A
RMS
TRUE
3.1.4. Potential Transformer Secondary Value (for 3V & V)
This screen displays “Pt-S” message followed by previously set PT secondary value on display.
For Eine 3V (3 phase) user can set PT secondary value from 100VLL to 500VLL & for
Eine V (single phase), user can set PT primary from 57.5(VLN) to 300VLN.