What to do if Ruskin Measuring Instruments airflow readings don't match T&B reports?
- KKyle JohnsonJul 31, 2025
If the airflow readings from your Ruskin Measuring Instruments do not match the reports from T&B, it could be due to turbulent airflow or air flowing in two directions through the plane of the air measurement station. Try using Automatic K factor Configuration and use 1 point calibration if only gain is required. If the flow is non-linear, use the two or three-point calibration feature. You may need to install additional probes to provide more sensing points.