24
Installation Procedure
Installation Procedure
English
Emergency Temperature Output (ETO) function
CAUTION
• InordertodeploytheETOfunction,theMIM-B14,anexternalcontactinterfacemodule,mustbeinstalledineach
indoorunit.
TheETOisaconceptofemergencyoperationofindoorunits.Iftheindoorunit1(mainindoorunit)stopsbecauseof
anerror,theindoorunit2(subindoorunit)startstooperate.
Basically,theindoorunit2operatesinthepreviousmode.[Forthefirsttimeoperation,itstartsin24°C(75°F)Auto
mode.]
Tosetmoredetailedoperationconditionsfortheindoorunit2,usetheS-netPro.
Setting up the ETO
Communication between
indoor and outdoor units
(F1 and F2)
Main indoor unit
Sub indoor unit
External contact
interface module
MIM-B14
Error output port (1, 2)
Contact input port (5, 6)
1 Mainindoorunit
Disabletheexternalcontactcontrol(Default).
ConnecttheS-netpro2toF1andF2.
EnabletheETOfunctionandsetthetemperatureandtime.
2 Subindoorunit
(Required)Enabletheexternalcontactcontrol(withtheinstallationoptionSEG14-ReverseControl).
ConnecttheS-netpro2toF1andF2.
Enabletheentrancecontrolandsetthemode,settemperature,andfanspeed.