30
Installation Procedure
Installation Procedure
Display contents SEG1 SEG2 SEG3 SEG4
K4 long
push
- Main micom version Year (Dec) Month (Hex) Date (Tens digit) Date (Units digit)
After short push 1 Inverter micom version Year (Dec) Month (Hex) Date (Tens digit) Date (Units digit)
After short push 2 E2P version Year (Dec) Month (Hex) Date (Tens digit) Date (Units digit)
After short push 3
Page 1 - AUTO
Page 2 - (SEG1,2 - Indoor : "A","0") (SEG3,4 - Address : ex) 00)
After short push 4
Page 1 - MANU
Page 2 - (SEG1,2 - Indoor : "A","0") (SEG3,4 - Address : ex) 00)
Long push K4 (Main micom ver.) → short push 1 more (Inv. micom ver.) → short push 1 more (E2P. ver.) → short push 1
more (Automatic address) → short push 1 more (Manual address) → short push 1 more (Main micom ver.) → ....... → Long
push K4 (View mode end)
7 Setting outdoor unit option switch and address manually
a Setting the option
• Press and hold K2 to enter the option setting.
(Only available when the operation is stopped)
– If you enter the option setting, display will show
the following.
– Seg 1 and Seg 2 will display the number for
selected option.
– Seg 3 and Seg 4 will display the number for set
value of the selected option.
• If you have entered option setting, you can shortly
press the K1 switch to adjust the value of the Seg 1,
Seg 2 and select the desired option.
Example)
• If you have selected desired option, you can shortly
press the K2 switch to adjust the value of the Seg 3,
Seg 4 and change the function for the selected option.
Example)
• After selecting the function for options, press and
hold the K2 switch for 2 seconds. Edited value of
the option will be saved when entire segments
blinks and tracking mode begins.
Option
item
Input
unit
SEG1 SEG2 SEG3 SEG4 Function
Channel
address
Main 0 0
A U
Automatic
setting
(Factory
default)
00~15
Manual
setting
Snow
accumulation
prevention
control
Main 0 1
0 0
Disabled
(Factory
default)
0 1 Enabled
Step for
Silence mode
Main 0 2
0 0
Disabled
(Factory
default)
0 1 Step1
0 2 Step2
0 3 Step3
Type of
Silence mode
Main 0 3
0 0
Automatic
Silence mode
(Factory
default)
0 1
Manual
Silence mode
Temperature
unit
Main 0 4
0 0
Celsius
(default)
0 1 Fahrenheit
Not applicable Main 0 5
0 0 Not applicable
0 1 Not applicable
DB68-11274A-00_IM_CAC Universal Outdoor_AA_EN.indd 30DB68-11274A-00_IM_CAC Universal Outdoor_AA_EN.indd 30 2021-09-14 오전 9:22:012021-09-14 오전 9:22:01