EasyManua.ls Logo

Samsung AC036BNZDCH - Page 32

Samsung AC036BNZDCH
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
32
English
Blower CFM tables
Installation
AC024BNZDCH
HP : 1/3 Default motor taps : High/Mid/Low = 4/3/2.
Motor Tap P(inwg) CFM Motor Tap P(inwg) CFM
1
0.1 543
4
0.1 811
0.2 512 0.2 810
0.3 479 0.3 797
0.4 446 0.4 773
0.5 411 0.5 737
0.6 374 0.6 689
0.7 337 0.7 630
0.8 298 0.8 559
2
0.1 564
5
0.1 894
0.2 542 0.2 890
0.3 518 0.3 870
0.4 492 0.4 837
0.5 464 0.5 789
0.6 433 0.6 726
0.7 400 0.7 649
0.8 366 0.8 558
3
0.1 669
0.2 649
0.3 628
0.4 606
0.5 582
0.6 559
0.7 534
0.8 508
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
200 300 400 500 600 700 800 900 1000
Q (CFM)
1
2
3
4
5
P (inwg)
DB68-11271A-02_IM_CAC Universal AHU Indoor_AA_EN_.indd 32 2022-09-15 오전 9:53:23