Setting an indoor unit installation option
In order to check and set the indoor unit installation option code use the wired remote controller and follow
the directions below.
1) Press the
and buttons at the same time for more than 3 seconds and then a Main menu will be
displayed.
2) Press the
/ button to select and then press button to enter a Sub-menu setting screen.
3) Press the
/ button to select and then press button to enter a Indoor unit installation option
code setting screen.
4) Press the
/ button to set the installation option code in order. Press button to go to the next
page.
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
0 2 RESERVED
Exterior temperature
sensor
Central control RESERVED
SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
1 Drain pump Use of Hot Coil Use of Electric Heater RESERVED Master / Slave
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
2 External control
External control
output
S-Plasma ion Buzzer
Number of hours
using filter
SEG19 SEG20 SEG21 SEG22 SEG23 -
3
Individual control of a
remote controller
Heating setting
compensation
RESERVED Away Set OFF Timer -
t The rst digit represents the page number and the remaining ve digits are installation option.
t The total option codes are 24 digits. You can set six digits at a time and it is distinguished by page
number (0, 1, 2, 3).
NOTE
SEG8 of the installation option code should be "2" when PCB is changed.
(Since the indoor unit is drained by a drain pump,installation option code setting is needed.)