4-8 Samsung Electronics
Model
AC035HBMDKH
Static Pressure(mmAq)
Option code for indoor unit
0≤ SP ≤2.5 01B06C-1C5084-272328-374000
2.5< SP <5 01B06C-1C50EB-272328-374000
5≤ SP <7.5 01B06C-1C5552-272328-374000
7.5≤ SP ≤10 01B06C-1C55CA-272328-374000
10< SP <12.5 01B06C-1C5A30-272328-374000
12.5≤ SP ≤15 01B06C-1C5A85-272328-374000
Model
AC052HBLDKH AC071HBLDKH
Static Pressure(mmAq)
Option code for indoor unit
0≤ SP ≤3 01C06C-1C5925-27323C-370000 01C06C-1C59E8-274750-370000
3< SP <4 01C06C-1C596B-27323C-370000 01C06C-1C5D2D-274750-370000
Model
AC071HBMPKH
Static Pressure(mmAq)
Option code for indoor unit
0≤ SP <3 01B06C-1C50D8-274750-373020
3≤ SP <6 01B06C-1C5541-274750-373020
6≤ SP <8 01B06C-1C5596-274750-373020
8≤ SP <10 01B06C-1C55DB-274750-373020
10≤ SP ≤15 01B06C-1C5A94-274750-373020
Model
AC052HBMDKH AC060HBMDKH AC071HBMDKH AC052HBMPKH
Static Pressure(mmAq)
Option code for indoor unit
0≤ SP ≤3
01B06C-1C50E6-
27323C-373000
01B06C-1C547F-
273C46-372005
01B06C-1C5580-
274750-371005
01B06C-1C50E6-
27323C-373000
3< SP <6
01B06C-1C544D-
27323C-373000
01B06C-1C55D5-
273C46-372005
01B06C-1C55E6-
274750-371005
01B06C-1C544D-
27323C-373000
6≤ SP <9
01B06C-1C55A4-
27323C-373000
01B06C-1C592B-
273C46-372005
01B06C-1C593C-
274750-371005
01B06C-1C55A4-
27323C-373000
9≤ SP <12
01B06C-1C591A-
27323C-373000
01B06C-1C5A71-
273C46-372005
01B06C-1C5A82-
274750-371005
01B06C-1C591A-
27323C-373000
12≤ SP ≤15
01B06C-1C5A70-
27323C-373000
01B06C-1C5AC8-
273C46-372005
01B06C-1C5AD9-
274750-371005
01B06C-1C5A70-
27323C-373000
With its phase control motor, you can adjust the indoor unit fan speed depending on the installation condition.
If the external static pressure is high so that the duct becomes longer or if the external static pressure is low so that
the duct becomes shorter, adjust the fan speed by referring the following table.
E. S. P(External Static Pressure) setting for phase control motor
t represents E. S. P(External Static Pressure) range of factory setting.
You don’t have to adjust the fan speed separately if the external static pressure of the installation place is in
. When it is out of
, input the appropriate option code.
t
If you input the inappropriate option code, error may occur or the air conditioner is out of order. The
option code must be inputted correctly by the installation specialist or service agent.