EasyManua.ls Logo

Samsung AC052MN4DKH - Page 71

Samsung AC052MN4DKH
101 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
4-36 Samsung Electronics
1. Replace the compressor wire. ĺ Power ON.
ĺ Check normal startup. ĺ End the service.
2. Replace the compressor wire. ĺ Power ON.
ĺ Check normal startup.
ĺ End the service.
3. Replace the compressor wire. ĺ Power ON.
ĺ Check normal startup. ĺ End the service.
No
1. Did compressor wires assem
bled in the appropriate color?
(U:Red, V:Blue, W:Yellow) ĺ
Check for disconnections of PCB and COMP.
2. Is the terminal in the compressor wire
ho
using firmly assembled?
3. Is there any fault of compressor wires
in disconnection or cutting?
Yes
Yes
$PNQSFTTPSTUBSUJOHFSSPSSPUBUJPOFSSPS&SSPS$PEF&&(cont.)
Continue
After replacing the Inverter PCB of the outdoor unit,
check for normal startup. ĺ End the service.
E461, E467 Error-related, EMI / outdoor unit Main / Indoor unit Main PCB do not replace!
ĺ This error is related to the compressor and Inverter PCB. (Not related
to the above PCB)
Ensure that the service valve is open!
ĺ When the service valve is closed, the defects may be caused by differential pressure when starting the compresso
r.

Other manuals for Samsung AC052MN4DKH