Samsung Electronics 4-7
Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Explanation PAGE MODE
RESERVED
Use of external
temperature
sensor
Use of central
control
RESERVED
Indication and Details
Indication Details Indication Details Indication Details Indication Details
02
0 Disuse 0 Disuse
1 Use 1 Use
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Explanation PAGE Use of drain pump
RESERVED RESERVED RESERVED
Master / Slave
Indication and Details
Indication Details Indication Details
Indication Details
1
0 Disuse
0 slave
1Use
1 master
2
Use +
3minute
delay
--
Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
Explanation PAG E
Use of external
control
Setting the
output of external
control
Virus doctor Buzzer control
Number of hours
using filter
Indication and Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
2
0 Disuse 0 Thermo on 0 Disuse 0
Use of
buzzer
2
1000 Hour
1
ON/OFF
Control
1
Operation
on
1
Use 1
Non
use of
buzzer
6 2000 Hour
2
OFF
Control
Option SEG19 SEG20 SEG21 -- -
Explanation PAG E
control of a remote
controller
Heating setting
compensation
-- -
Indication and Details
Indication Details Indication Details Indication Details -- -
3
0 or 1 Indoor 1 0 Disuse
-- -
2 Indoor 2 1 2°C
3 Indoor 3
2 5°C
4 Indoor 4
5. Press the button to save and complete the option setting.
6. Press the
button to exit to normal mode.
t Press button anytime during setup to exit without setting.
t Option code will not be applied if you don't press
button.
t Setting Installation option code is available only with a master wired remote controller.
t Setting Installation option code is available when there is one on one connection between a wired
remote controller and an indoor unit.
NOTE