EasyManua.ls Logo

Samsung AC071RNNDKG - Cleaning and Maintaining

Samsung AC071RNNDKG
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13
Installation Procedure
English
• Ifitisnecessarytoincreasetheheightofthedrain
pipe,installthedrainpipestraightwithin300mm
fromthedrainhoseport.Ifitisraisedhigherthan550
mm,theremaybewaterleaks.
Band joint
300 mm or
less
550 mm or
less
20 mm or more
1/100 or more
Drain hose
Ceiling
• Donotgivethehoseanupwardgradientbeyondthe
connectionport.Thiswillcausewatertoflowbackwards
whentheunitisstopped,resultinginwaterleaks.
Under gradient
Ceiling
• Donotapplyforcetothepipingontheunitsidewhen
connectingthedrainhose.Thehoseshouldnotbe
allowedtohangloosefromitsconnectiontotheunit.
Fastenthehosetoawall,frameorothersupportas
closetotheunitaspossible.
Support pieces
1 to 1.5 m
1/100 or more
Ceiling
• Installhorizontally.
Indoor unit
Be horizontal
Flexible hose
• Max.allowableaxisgap.
Indoor unit
Max. 20 mm
• Max.allowablebendingangle.
Max. 30˚
Indoor unit
NOTE
• Ifaconcentrateddrainpipeisinstalled,refertothe
figurebelow.
CAC R-32_Mini 4way_IM_DB68-08129A-00_EN_20181211.indd 13 2018/12/11 11:30:21

Other manuals for Samsung AC071RNNDKG

Related product manuals