Troubleshooting
Samsung Electronics 4-23
4-3-16 The others
1. E465 : Compressor over load error
t*GBDPNQSFTTPSXPSLTJNQSPQFSMZDIBOHFUIFDPNQSFTTPSBOEDIFDLJGJUXPSLTQSPQFSMZ
¤ If a compressor is normal, check the assembly between Heatsink-Inverter PBA. If it is fine, change Inverter PBA.
2. E468 : Current sensor error
t
Check EEPROM data.
t
Check PCB operates properly.
3. E471 : Oudoor EEPROM error
t
Upload EEPROM on Outdoor unit Main PBA.
4. E474 : IPM(IGBT Module) or PFCM Temperature sensor Error
t
E500 : IPM is over heated
t
Check IPM is well assembled to heatsink
t
Check whether inlet port is clogged.
t
Change IPM if it is defective one
5. E554 : Gas leak error
t
Check refrigerant charge
t
Check Indoor EVA sensor
t
Check Service valve is open.
t
Check the pipes and wires correctly connected.
6. E556 : Capacity miss match between indoor and outdoor
t
Check the model name of indoor and outdoor unit and set option code on indoor unit again.
7. Outdoor overload protection control (at the stop of the compressor.) : E404
t
Check whether the fan and the motor operate normally.
t
Check the operation of EEV.
t
Check the temperature sensor of the indoor unit heat Exchanger.
t
Check the indoor unit inlet blocking.