safety information _19
ENGLISH
Power supply cords of parts of appliances
for outdoor use shall not be lighter than
polychloroprene sheathed flexible cord.
(Code designation IEC:60245 IEC 57 /
CENELEC:H05RN-F or IEC:60245 IEC 66 /
CENELEC: H07RN-F)
The unbalanced power must be maintained
within 10 % of supply rating among whole
indoor units.
If the power is unbalanced greatly, it may
shorten the life of the condenser.
If the unbalanced power is exceeded over 10%
of supply rating, the indoor unit is protected,
stopped and the error mode indicates.
To protect the product from water and possible
shock, you should keep the power cable and
the connection cord of the indoor and outdoor
units in the protection tube.
Connect the power cable to the auxiliary circuit
breaker.
You must keep the cable in a protection tube.
Keep distances of 50mm or more between
power cable and communication cable.
Maximum length of power cable is decided
within 10 % of power drop. If it exceeds,
you must consider another power supplying
method.
NASA_Cassette type_IB_EN_03568A-07.indd 19 2016-04-06 오전 9:01:04