installing your air conditioner _53
ENGLISH
Setting an indoor unit address and installation option
Option SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
Explanation PAGE
Individual control of
a remote controller
Heating setting compensation / Removing
condensated water in heating mode
EEV Step of stopped
unit during oil return/
defrost mode
Motion detect sensor -
Remote
Controller
Display
Indication
and Details
Indication Details Indication Details Indication
Details
Indication Details Indication Details
Heating Setting
Compensation
Removing
Condensated Water
in Heating Mode
3
0 or 1
channel
1
0 Default
4)
Disuse
0
Default
value
0 Disuse
1 2 °C Disuse 1
Turn out in 30min.
without motion
2
channel
2
2 5 °C Disuse
1
Oil return
or Noise
decreasing
in defrost
mode
2
Turn out in 60min.
without motion
3
channel
3
3 Default
4)
Use
5)
3
Turn out in 120min.
without motion
4
channel
4
4 2 °C Use
5)
4
Turn out in 180min.
without motion
5 5 °C Use
5)
5
Turn out in 30min.
without motion or
*advanced function
6
Turn out in 60min.
without motion or
*advanced function
7
Turn out in 120min.
without motion or
*advanced function
8
Turn out in 180min.
without motion or
*advanced function
*Advanced function: Controlling cooling/heating current or power saving with motion detect.
1)
Minimizing fan operation when thermostat is o
- Fan operates for 20 seconds at an interval of 5 minutes in heat mode.
2)
1: Fan is turned on continually when the hot water heater is turned on,
3: Fan is turned o when the hot water heater is turned on with cooling only indoor unit
Cooling only indoor unit: To use this option, install the Mode Select switch (MCM-C200) on the outdoor unit and x it as cool mode.
3)
When the following 2 or 3 is used as external heater On/O signal, the signal for monitoring external contact control will not be output.
2: Fan is turned on continually when the external heater is turned on,
3: Fan is turned o when the external heater is turned on with cooling only indoor unit
Cooling only indoor unit: To use this option, install the Mode Select switch (MCM-C200) on the outdoor unit and x it as cool mode.
❋
If Fan is set to o for cooling only indoor unit by setting the SEG9=3 or SEG15=3, you need to use an external sensor or wired remote controller sensor to detect
indoor temperature exactly.
4)
Default setting value
- 4Way Cassette, Mini 4Way Cassette: 5 °C
- Other indoor units: 2 °C
5)
This function can be applied to 4 Way Cassette and Mini 4 Way Cassette only. If the air conditioner operates the heating mode immediately after nishing the cooling
mode, the condensated water in the drain pan becomes water vapor by the heat of the indoor unit heat exchanger. Since the water vapor might be condensed on
the indoor unit, which may fall into a living space, use this function to get rid of the water vapor out of the indoor unit by operating the fan (for maximum 20 minutes)
even when the indoor unit is turned o after cooling mode is turned to heating mode .
NASA_Cassette type_IB_EN_03568A-07.indd 53 2016-04-06 오전 9:01:24