Samsung Electronics 2-53
Indoor Unit(cont.)
Q
Wall Mounted type (MAX With EEV)
Model AM032MNQDCH/AA
Power Supply Φ,#,V,Hz
1,2,208-230,60
Mode *1) -
HP / HR
Performance Capacity
Cooling*2)
kW
Btu/h
31,700
Heating*3)
kW
Btu/h
33,400
Power
Power Input
Cooling W
66
Heating W
76
Current Input
Cooling A
0.47
Heating A
0.54
Fan
Type -
Crossflow Fan 107*L485, 2EA
Motor
Type -
BLDC
Output W 58
Number of unit -
1
Airflow Rate
Cooling(High)
/mim
22.5
Heating(High)
/mim
25.0
Piping Connections
Liquid Pipe
Φ,
9.52
Φ,inch
3/8כ
Gas Pipe
Φ,
15.88
Φ,inch
5/8כ
Drain Pipe Φ,
ID 18 HOSE
Field Wiring Power Source Wire Below 20m/over 20m mm²
1.5 ~ 2.5
Transmission Cable mm²
0.75 ~ 1.50
Refrigerant
Type -
R410A
Control Method -
EEV INCLUDED
Sound Sound Pressure*4) Cooling/Heating dBA
55/56
Dimensions
Net Weight
19
Shipping Weight
22
Net Dimensions (W x Hx D)
1279*345*229
Shipping Dimensions (W x Hx D)
1352*420*326
Functions
Auto Restart -
O
Auto Swing -
O
Group/Individual Control -
O
External Contact Control -
O
Trouble Shooting by LED -
O
Standard Accessories
Installation Manual -
O
Operation Manual -
O
Pattern Sheet for Installation -
X
Flexible Drain Hose -
O
Filter / Safety Grille -
Filter (Washable)
Wireless Remote Controller -
MR-EH00
Optional Accessories
Wireless Remote Controller -
-
Wired Remote Controller Simplified -
MWR-WE10N
External Contact Interface Module -
MIM-B14
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Nominal cooling capacities are based on;
- Indoor temperature : 27˚C DB, 19˚C WB
- Outdoor temperature : 35˚C DB, 24˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*3) Nominal heating capacities are based on;
- Indoor temperature : 20˚C DB, 15˚C WB
- Outdoor temperature : 7˚C DB, 6˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications may be subject to change without prior notice for product improvement.