EasyManua.ls Logo

Samsung AM024FNLDCH/AA - Dislocation error of Compressor SUMP Temperature (oil temperature) Sensor

Samsung AM024FNLDCH/AA
404 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
Samsung Electronics 4-87
4-4-44
: Dislocation error of Compressor SUMP Temperature (oil temperature) Sensor
Indoor unit display
×
(Operation)
(Timer)
(Fan)
(Filter)
×
(Defrost)
(digital compressor or fixed compressor 1)
Sump (oil) temperature sensor dislocation error
Criteria
Cause of problem
Refer to how to determine below
Outdoor unit display
1. How to diagnose
1) If the Sump temperature right before the start of compressor = Tsump.ini, current compressor's SUMP temp =Tsump. real,
When the difference between Tsump.ini and Tsump.real is an absolute value so that it cannot be more than 2˚C,
In other words, the condition of Tsump.real-Tsump.ini<2˚C has been satisfied for 60 minutes since a compressor started, it is diag-
nosed as an error.
After 60 minutes of compressor operation, there will be no Sump sensor dislocation detection.
2. How to check
1) Check if a sensor of the relevant compressor has been dislocated in accordance with error code, assemble and correct the error.

Table of Contents

Related product manuals