Troubleshooting
Samsung Electronics 25
4-3-3 Communication error (1 minute) between Main MICOM of an Outdoor unit INV
(Error Code : E203 )
1. Check items
1) Is there power on outdoor unit inverter PBA?
2) Connect the power cable/check the fuse.
3) Is there any problem on communication cable between outdoor unit inverter (CN31) Main PBA (CN39)?
4) Check the communication cable connection.
2. Check procedure
Yes
End service
No
Is there any communication error?
Connect the power cable/check the fuse
1. Is there any problem on the power cable between
outdoor unit main EMI PBA?
2. Is there any problem on the power cable between
outdoor unit inverter EMI PBA?
3. Is the fuse (FUSE100) on outdoor unit inverter PBA
normal? (Short-Normal, Open-Abnormal. Only applies to
RDSSSHXHS series)
No
Yes
Turn off the power and turn it on again after 30 seconds.
Change the outdoor unit inverter or main PBA
1. If the 7-segment on the outdoor unit main PBA shows E203
error, change the PBA outdoor unit main PBA is normal
2. When the LED on the outdoor unit inverter is shown as
following; Red-On, Green-On, Orange-Blinking and if the
7-segment on the outdoor unit main PBA does not display
anything, change the main PBA Outdoor unit inverter
PBA is normal
[Check list for model which uses 1 phase power]
[Check the LED on inverter PBA]
Check the communication cable connection
No
Yes
[Check list for model which uses 3 phase power]
1 2 2 3
[Check list for model which uses 3 phase power]
[Check list for model which uses 1 phase power]
Is there power on Inverter PBA?
1. Inverter PBA connector part (CN31)
1 2
Inverter PBA connector (CN31)
2. Main PBA connector (CN39)
MAIN PBA connector (CN39)
Is there any problem on
communication cable between outdoor unit inverter
(CN31) Main PBA (CN39)?
[Model which uses 3 phase
power Inverter PBA LED
confirmation part]
[Model which uses
1 phase power Inverter PBA
LED confirmation part]
[7-segment on
Main PBA (Common)]

Related product manuals