Troubleshooting
Samsung Electronics 31
4-3-9 Comp. down due to a discharge temperature sensor of a compressor
(Error Code : E416)
1. How to check
Is the discharge sensor
resistance of the compressor
normal? (refer to E251)
Test operation
Are service valves open?
Does indoor/outdoor EEV
operate well?
Is there
any clogged place in the piping.
(ex. filter)?
Replace discharge temperature sensor
Open the service valve
Check the relevant EEV
Check the piping
Connect S-net and Manifold gauge
(Mandatory)
No
No
No
Yes
Yes
Yes
Yes
No
Check the amount of
refrigerant.