Troubleshooting
40 Samsung Electronics
4-3-18 Electric current error / PFC over current error (Error Code : E462, E484)
1. Check items
1) Check the power and restarting after power reset
2) Check the outdoor unit installation and environments
Check if the outdoor unit inverter PBA related wires
are disconnected. Check the installation environment
3) Check for indoor unit installation environment
4) Check for open service valve
2. Check procedure
Error CODE Error description Related model
E462 Outdoor unit total current error
RD
SSSS
HXG
S
series,
RD
SSSSS
XE
S
series
E484 Outdoor unit PFC overload error
RD
SSSSS
XE
S
, RD060
SSSSS
,
RC072
SSSS
series only
Yes
Check the outdoor unit installation and
environment Check for normal operation
End service
1. Check for wire disconnection related to outdoor
unit inverter PBA
2. Remove the obstacles on outdoor unit air inlet
and secure enough space
3. Remove the obstacles on outdoor unit air outlet
and secure enough space
Check the indoor unit installation and
environment Check for normal operation
End service
1. Remove obstacles on air inlet and secure
enough space
2. Remove obstacles on air outlet and secure
enough space
No
Is the outdoor unit installed correctly?
Change the outdoor unit inverter PBA and check for normal
operation End service
Yes
No
Is the indoor unit installed correctly??
Yes
Replace the compressor
No
Yes
Turn off the power and turn it
on again after 30 seconds
Open the valve
No
Is the service valve completely open?
Is the compressor operating normally?
Check list for model which uses
3 phase power.
Check list for model which uses
1 phase power.